• The communication subsystem between PLC processor and I/O subsystem shall be dual<br />

redundant.<br />

• The communication munication subsystem between processor subsystem and PLC console shall be dual<br />

redundant, consisting of two separate communication interfaces and two buses, each one<br />

configured in redundant mode.<br />

• No hardwired alarm system is required. All the alarms are to be displayed in OWS of PLC<br />

with multi tone buzzer and with alarm history provision.<br />

• The software provided at the time of supply should be of latest version.<br />

• Necessary license to be provided along with the software.<br />

• The OS (Operator Station) desk and opera operator tor chair to be supplied by the bidder.<br />

4.11 UNINTERRUPTIBLE POWER SYSTEM (UPS)<br />

General System Description<br />

The required kVA, 50 Hz, single phase UPS system shall provide continuously operating<br />

uninterrupted power supply to critical AC loads such PLC PLC, , instrumentation, etc.<br />

The capacity of UPS shall be suitable to feed power requirement of the PLC which shall control<br />

and monitor all the drives/mechanism of proposed additional coal handling system.<br />

The UPS system shall include but not necessarily limited to the following equipment:<br />

• One 100% rated battery bank<br />

• One set of Float Charger (FC) and one set of Float cum Boost Charger (FCBC) complete<br />

with associated incoming AC switchgear.<br />

• Two nos. 100% capacity inverter banks.<br />

• One no. DC switchgear, cconnecting<br />

onnecting above and also inverter banks stated above<br />

• One no. 3 phase to 1 phase transformer and associated AC switchgear, 230V, 1 phase<br />

voltage stabilizer and backup source static switch.<br />

• One no. 240 V UPS ACDB<br />

• One no. four way manual bypass switch<br />

• Static switches<br />

• All inter connecting cables/wiring with connection accessories and other required items<br />

to make the system complete.<br />

Mode of Operation<br />

Normal Mode<br />

During the normal operation the UPS shall be used to provide power to the critical loa loads. The<br />

primary AC source shall be used to supply power to the rectifier charger. Two (2) no. chargers<br />

shall feed regulated DC power to their individual inverter banks and simultaneously float<br />

charge the backup batteries.<br />

Emergency Mode<br />

Technical Specification:Sec-6, Electrical<br />

Page 45 of 97