Technical details of HT transformer and other switch gear will be submitted to NALCO / RITES<br />

for its approval. The conductor for 33KV line shall be of AACSR<br />

CSR (dog/Rabbit) type.<br />

The HT transformer (33KV/ (33KV/0.44KV) shall ll be located in the near the wagon tippler area. The<br />

switch gear will be designed in conformity to CEA norms having provision of LA, PT, CT, ISO etc.<br />

Fencing and development of switch gear will be the scope of the bidder. The switch gear will<br />

be located near wagon tippler area.<br />

Room size to be decided by the bidder to house all required equipments (HT & LT switch<br />

gears) at the ground floor.<br />

WT Control room and operating panel will be located aat<br />

t first floor of the building.<br />

Bidders are also advised to visit the site and assess the actual quantum of work to be done for<br />

this diversion and include accordingly.<br />

The operation of the WT SYSTEM plant shall be monitored and controlled from the proposed<br />

WT control rooms by means of VDU operator interface on a microprocessor based<br />

programmable logic controller (PLC). The system shall be envisaged for the purpose of initial<br />

operation, protection and interlock, data acquisition, close loop control, data a aarchiving,<br />

etc for<br />

fully automatic operation. The system shall be capable of monitoring and displaying the status<br />

of equipment, including the analog and digital signal displaying of status in the form of<br />

diagram, trend bar chart, overview, logs, etc with th the e help of CRT, keyboard, mouse and<br />

printers.<br />

Necessary hardware and software license of the proposed PLC shall be provided provided. PLC<br />

programme, ladder logic and control philosophy shall be submitted by the bidder for approval<br />

of NALCO/RITES.<br />

The preferred make of PLC shall be GE GE-FANUC make.<br />

33 kV Unit Vacuum Circuit Breaker<br />

33 kV indoor Vacuum Circuit Breaker shall conform to the following technical particulars:<br />

i) Type<br />

Indoor, Vacuum type, electrically operated,<br />

trip free type, panel mounted<br />

ii) Quantity<br />

iii) System Voltage 33 kV<br />

iv) Maximum system voltage 36 kV<br />

v) Continuous current As per requirement<br />

vi) Rated short time current rating 31.5 kA for 3 sec<br />

vii) Interrupting capacity at 36 kV 31.5kA<br />

Technical Specification:Sec-6, Electrical<br />