2.4.5 Condenser: Air cooled type<br />

2.4.6 Fan: Forward curved centrifugal fan<br />

2.4.7 Filter: High efficiency filter<br />

2.4.8 Cooling Coil<br />

(a) Type: Direct Expansion<br />

(b) Material: Copper<br />

(c) Fins: Aluminum mechanically bonded.<br />

2.4.9 Refrigerant: Piping Copper<br />

2.4.10 Insulation for PAC parts: Expanded polyethylene of density at least 15 kg/cub.m.<br />

2.5.0 Filters<br />

2.5.1. Metallic Filters<br />

(1) Max. air velocity: 2m/sec.<br />

2.5.2 HDPE filters<br />

(1) Efficiency: 90% down to 5 microns<br />

(2) Max. velocity: 2.5 m/sec.<br />

(3) Testing: As per BS 2831 / Sqv.<br />

2.5.3 High Efficiency Filter<br />

(1) Efficiency: 99.9% down to 5 microns.<br />

(2) Pr. drop across: 10 mm W.C.<br />

(3) Testing: As per BS 2831 / Sqv.<br />

2.6.0 Insulation for A/C Ducting Resin Bonded Mineral wool as per IS:8183<br />

2.6.1 Density: 24 kg/cub.m<br />

2.6.2 Thermal conductivity: 0.49 mw/cm deg.C<br />

18.0 DESIGN OF CONVEYOR GALLERIES AND JUNCTION HOUSES<br />

18.1 Design Considerations<br />

a) The general parameters for conveyor galleries shall conform to the provision of IS : 11592 11592-<br />

1985 unless specified otherwise in Technical Specifications. The structures shall be designed<br />

so as to meet functional requirem requirements ents and shall provide space for operation, maintenance<br />

and removal of machinery and give the workers good and safe environment.<br />

b) Gallery floors shall be of chequered plates supported on steel beams.<br />

c) Steps shall be provided with (rise not exceeding 130 mmm<br />

m along the walkways if the gallery<br />

slope exceeds 12°. . In case the slope of gallery is between 66°<br />

to 12°, , suitable ribs (without any<br />

sharp edges) shall be provided on floor at 250 to 300 mm intervals.<br />

d) Roof and side walls of conveyor galleries shall be covered with Aluminium industrial<br />

troughed sheets. . with a provision of gap of 300 mm below roof and 150 mm from top of<br />

floor level on the side wall for ventilation.<br />

e) Adequate provision for natural light in inside side conveyor gallery shall be made through side walls<br />

by providing translucent sheets (FRP sheets as per IS: 12866 12866-1989). 1989). Every sixth sheet on side<br />

wall shall be FRP sheet and shall be staggered on opposite wall.<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />

Page 54 of 64