Degree of protection for motor and bearings shall be IP IP-55 55 for indoor use aand<br />

IP-55 with<br />

removable rain canopy for outdoor use.<br />

Vibration monitor with contacts shall be provided at the DE end of motor bearing for motors<br />

of ratings 1000 kW and above. On line vibration measurements shall be provided for larger<br />

and critical motors.<br />

All motors shall be provided with Bearing (DE & NDE) temperature detectors and 6 nos. stator<br />

winding temperature detectors, RTDs for monitoring alarm and trip conditions. Temperature<br />

shall be displayed on VDU's. RTD's shall be of PT100 type and suitable for digital scanner or<br />

PLC input requirement.<br />

Digital igital type bearing temperature indicator for all motors shall be provided for local<br />

measurement with adjustable alarm contacts.<br />

Each terminal box shall have fault withstand capacity equal to at least rated short circuit level<br />

of the system voltage for 00.25<br />

.25 sec and shall have pressure relief device. Terminal boxes shall<br />

be suitable for termination of FRLS, XLPE cables with cable end seals. Separate terminal boxes<br />

shall be provided for space heaters, RTDs for winding/ bearings temperatures, vibration<br />

monitors etc.<br />

All terminal boxes shall be provided with two earthing studs for termination of protective<br />

earth conductor. Box covers shall be provided with handle to facilitate easy removal.<br />

Low kW range machines may be of TEFC (IC0141) design. For higher rrating,<br />

ating, type of cooling<br />

shall be CACA (IC0151). General accessories like flow switches, space heater, terminal boxes,<br />

drain plug, dowel pipe cable lugs, glands clamp etc. shall be provided.<br />

Vibration intensity shall be limited to values as stipulated in tthe<br />

he IS. Motor shall be designed to<br />

withstand the vibration produced by the driven equipment. Continuous noise level should not<br />

exceed 75 dBA at a distance of 1.0 m from the motor body.<br />

Electrical design shall be same as in case of low voltage induction mot motors ors except the following:<br />

All motors shall have class F insulation but with total permissible temperature limited to 1300C<br />

(as measured by resistance method). Starting current of the drives shall be limited to six times<br />

of full load current.<br />

Motors of rating 1000 kW and above shall be provided with differential protection. Matching<br />

CT and cabling up to switchgear shall be provided by the Bidder.<br />

Motors shall be capable of withstanding locked rotor current at 110 % rated voltage for at<br />

least 2.5 sec (for or motors having staring time up to 20 sec) or 5 sec (for motors having staring<br />

time more than 20 sec) longer up to than starting time under rated load condition at 80 %<br />

voltage. If above condition is not possible then, centrifugal type speed switch to be provided<br />

Technical Specification:Sec-6, Electrical<br />