Internal control wiring shall be by 1100V V grade PVC insulated, single core stranded copper<br />

conductor of minimum cross section 2.5 sq.mm. for CTs and space heater circuits and 1.5<br />

sq.mm for other circuits. For CT secondary wiring, disconnecting type terminal blocks (CAD<br />

type) shall be considered. .<br />

For external terminations, , DIN rail mounting type bakelite type terminal blocks shall be used<br />

complete with insulated barriers, stud type terminals, washers, nuts and lock nuts and<br />

identification strips. Power and control terminals segregated.<br />

Other accessories<br />

Following items shall be provided for the MCCs under the scope of the Bidder:<br />

Breaker lifting/handling trolley (for ACBs) : 1 No. per MCC Room<br />

Breaker racking handle (for ACBs) : 4 Nos. per MCC Room<br />

Panel key (if applicable)<br />

: 5 Nos. per MCC Room<br />

Selection of power components & wiring for continuous duty cage motor drives is given below:<br />

Motor<br />

Rating<br />

at S1<br />

Duty<br />

(KW )<br />

Up to<br />

3.7<br />

5.5<br />

7.5<br />

Minimu<br />

m<br />

rating<br />

of<br />

MCCB<br />

*<br />

*<br />

*<br />

11 *<br />

15 *<br />

18.5 *<br />

22 *<br />

30 *<br />

37 *<br />

45 *<br />

55 *<br />

75 *<br />

90 *<br />

110 *<br />

125 *<br />

135 *<br />

160 *<br />

Technical Specification:Sec-6, Electrical<br />

Minimum<br />

rating of<br />

contactor<br />

(AMPS) AC3<br />

duty<br />

25<br />

40<br />

40<br />

Minimum size for internal<br />

power connections<br />

Copper<br />

wire<br />

(sq.mm)<br />

Aluminium flat<br />

(mm x mm )**<br />

*Minimum rating of MCCB shall be selected to achieve type ‘2' protection.<br />

4<br />

4<br />

6<br />

40 6 -<br />

63 10 -<br />

-<br />

-<br />

-<br />

Minimum size of<br />

power cable<br />

Aluminium<br />

(sq.mm)<br />

4x 2.5(copper)<br />

4x 2.5(copper)<br />

4 x 6<br />

4 x 16<br />

4 x 16<br />

63 16 12 x 2 3.5 x 35<br />

63 16 12 x 2 3.5 x 35<br />

100 25 12 x 2 3.5 x 70<br />

100 35 15 x 3 3.5 x 70<br />

160 50 15 x 3 3.5 x 95<br />

160 70 20 x 3 3.5 x 120<br />

200 95 20 x 5 3.5 x 185<br />

400 20 x 5 3.5 x 185<br />

400 30 x 5 2(3.5 x 120)<br />

400 40 x 5 2(3.5 x 120)<br />

400 40 x 5 2(3.5 x 120)<br />

400 40 x 5 2(3.5 x 185)<br />