CTs for back up earth fault (51N) as well as for restricted earth fault (64) shall be provided on<br />

the neutral end.<br />

Neutral bushing CT shall be re removable movable at site without opening transformer tank cover/active<br />

part. Secondary leads of 4 sq.mm shall be brought to a weatherproof terminal box and from<br />

there to the marshalling box.<br />

Neutral bushing CTs of suitable ratio, class and adequate burden shall be provided by the<br />

Bidder to cater to the requirement of all standard protection associated with the transformer<br />

of this capacity. CTs for REF shall be PS class.<br />

4.7.8 Marshalling Box<br />

Enclosure mounted marshalling box to be supplied with all controls instruments, protection,<br />

accessories & fitting as required for the transformer and its associated ancillaries. The box<br />

shall be made of 2 mm sheet steel with IP 54 degree of protection.<br />

Sheet heet steel marshalling box of dust dust-proof proof design shall be provided to accommodate<br />

temperature measurement as well as control system, as may be necessary. The box shall be<br />

mounted on the transformer enclosure and shall be provided with internal lighting, spa space<br />

heater and thermostat with their controls accessible from outside.<br />

The box shall be provided with suitable hinged steel doors at the front and all equipment shall<br />

be so placed as to accessible from the front. Provision shall be made for padlocking the doors.<br />

Suitable glazed windows shall be provided at appropriate positions to give an unrestricted<br />

view of the temperature indicators etc, without opening the door.<br />

All initiating tiating “contacts” of shall be wired up to the terminal block in the box. All control wiring<br />

shall be with 1.1kV grade stranded PVC insulated armoured copper cable of 2.5 sq.mm.<br />

Terminal blocks shall have 20% spare capacity.<br />

The external connections betw between een the apparatus on the transformer and the marshalling box<br />

shall be done with suitable heat resisting copper conductor cables of core size not less than<br />

2.5 sq. mm. The cables required to connect the marshalling box and transformer accessories<br />

shall be adequately dequately protected against mechanical damage. There shall be no joints or tappings<br />

between two terminations of any cable. Not more than two terminations shall be made at any<br />

one terminal. All terminations at various devices and terminal blocks shall be pr provided with<br />

plastic ferrules having engraved numbers. All terminals and links shall be so arranged as to<br />

facilitate easy checking and testing of relays, instruments etc. Provision shall be made for<br />

termination of power cables as well as multi multi-core control cables in the marshalling box.<br />

The control circuit terminal blocks provided for external cable connections shall be provided<br />

with screw type terminals and shall be complete with terminal screws, links, cable carries etc,<br />

Each terminal block shall have 20 20% % spare terminals and all wiring shall be such that it is easily<br />

identifiable and accessible for maintenance.<br />

Technical Specification:Sec-6, Electrical<br />

Page 35 of 97