• Sequence module<br />

• Zero speed/over speed monitor as applicable<br />

• V/f control<br />

• Current limiter<br />

• Counter current/ regenerative braking unit as applicable<br />

• active electronic components used shall be of industrial grade hermetically sealed<br />

• Regulated power supply for reference setting:<br />

Voltage variation of (+/-) ) 0.1 % with an input variation of +10% - 15%<br />

Steady state regulation of (+/ (+/-)0.25% % guaranteed against 100 to 200 % load disturbance and +<br />

3%, -6% 6% input supply frequency variation.<br />

• Facility to accept speed reference from computer/ programmable controller<br />

Construction features<br />

• Floor mounted, free standing<br />

• Dust and vermin proof<br />

• Sheet steel clad<br />

• Minimum 2.5 mm thick for panels.<br />

• Minimum 2.0 mm thick for doors and side covers.<br />

• Suitable to withstand vibrations to be encountered in steel plant application.<br />

• Cubicles with illumination lamps, door switches, space heaters and adequate sockets<br />

for soldering.<br />

• All control blocks plug –in-type with necessary test sockets.<br />

• Units shall be self contained and serviceable.<br />

Enclosure and Ventilation<br />

• Enclosure conforming to IP IP-52 or more with weather proof enclosures<br />

• Units shall be provided with cooling fans and louvers at the bottom sides. All louvers shall<br />

have fine mesh behind them.<br />

• Ventilation through individual ventilation ducts, from bottom not acceptable.<br />

4.9 RELAY PANELS<br />

Relay panels (RP) housing aux. contactors, timers, relays, etc. shall be provided for equipment<br />

control, sequential control, monitoring, safety alarm signals, annunciation signals, interlocking<br />

of drives ,signal exchange, interface with future system etc. shall be provided. Constructional<br />

features of R.P. shall be similar to MCC. At least 10 % spare auxiliary contactors, timers &relays<br />

shall be provided in the relay panel whose contacts and coils shall be wired up to terminals. terminals.10<br />

% spare terminals shall als also be provided. 10 % of auxiliary contactors, timer and relays shall be<br />

provided as spares which will be wired upto terminals.<br />

4.10 PROGRAMMABLE LOGIC CONTROLLERS (PLC)<br />

Power supply system<br />

Technical Specification:Sec-6, Electrical<br />

Page 41 of 97