iii) LED status indication iv) BCD input units suitable for four digit input<br />

• Analog input units shall be as follows:<br />

i) Suitable for 4-20 20 mA / 00-10V<br />

/ +/-10V inputs<br />

ii) With necessary A/D converter<br />

• Pulse/ frequency input module shall have range up to 50 kHz. For very high frequency<br />

applications, the range shall be up to 1 MHz.<br />

Output units<br />

• High Density (32/16 Channel), modular and plug plug-in type<br />

• Discrete output units shall be as follows:<br />

i) Opto-isolated isolated outputs with insulation level of 1.5 kV<br />

ii) Rated for 24V DC, 2A<br />

• Power devices like contactor or odd voltage actuating device shall b bbe<br />

actuated through<br />

relays<br />

• LED status indication<br />

• BCD output units shall be as follows:<br />

i) Suitable for four digit output<br />

ii) Rated to drive seven segment LED displays<br />

iii) With insulation level of 1.5 kV<br />

• Analog outputs shall be as follows<br />

i) Suitable for 4-20mA/ 20mA/ 00-10V/<br />

+/-10V 10V outputs capable of driving Digital / Analog Panel<br />

Meters<br />

ii) With necessary D/A converters<br />

iii) With insulation level of 1.5 kV<br />

iv) Any special requirement to control field devices shall be met by using separate<br />

interface modules<br />

PC based programming unit:<br />

• PC used for Programming Terminal shall be commercial grade and latest available in the<br />

Suitable for developing programs in ladder diagram/ block diagram or statement form<br />

• With facility for loading the program from floppy<br />

• The terminal shall be capable of developing multiple programs offline without connecting to<br />

the programmable controller.<br />

Self diagnostic features<br />

• Parity errors, cycle errors and under voltage<br />

• Failure in central processor unit, memory and power sup supply.<br />

• Indication of type of failure<br />

• Automatic turning OFF of all outputs or optionally holding of all outputs in their last state on<br />

failure detection.<br />

Additional features<br />

• Fully pre-programmed<br />

• Connection of field devices with input units throu through ordinary multi-core<br />

copper control<br />

cables of 1.5 sq. mm size, upto a length of 500 m.<br />

Technical Specification:Sec-6, Electrical<br />

Page 43 of 97