(b) In toilets: Ground glass of minimum thickness 4 mm.<br />

(c) In other areas: Toughened glass of minimum thickness 4 mm The above mentioned glass<br />

thickness are bare minimum only and actual thickness will depend on the panel size of the<br />

glazing to be provided.<br />

21.0 False Ceiling<br />

All air - conditioned areas, shall be provided with the suspended permanently colour coated<br />

aluminium false ceiling system with corrosion resistance aluminium alloy panels of m mminimum<br />

thickness 0.5 mm. 50 mm thick mineral wool insulation (as per IS: 8183) having a density of<br />

32 kg/cum for glass wool or 48 kg/cum for rock wool, bound in polythene bags shall be laid<br />

on top of panels. Additional hangers and height adjustment clips shall be provided for<br />

returns air grills, light fixtures, A. C. ducts etc. Suitable M. S. channel (Minimum ISMC 75)<br />

grid shall be provided above the false ceiling level for movement of personnel to facilitate<br />

maintenance of lighting fixtures, AC ducts etc. Under deck insulation shall be provided on<br />

the ceiling (underside of roof slab) and underside of floor slab of air - conditioned areas<br />

depending upon the functional requirements. This under deck insulation shall consist of 50<br />

mm thick mineral wool insulat insulation ion mat conforming to IS: 8183 having a density of 32 kg/cum<br />

for glass wool or 48 kg/cum for rock wool, backed with 0.05mm thick aluminium foil and 24G<br />

x 25 mm mesh wire netting and shall be fixed to the ceiling with 14G wire ties.<br />

22.0 Acid / Alkali Resis Resistant Lining<br />

Battery Room For Floor and dado, bitumen primer followed by 12 mm thick bitumastic 6 mm<br />

thick potassium silicate mortar bedding and 20 mm thick A. R. tiles shall be provided. Dado<br />

height shall be minimum 2.0 m from floor. M. S. Grating / Cheque Chequered red plate cover and any<br />

other steel structure likely to come in contact with chemicals shall be provided with epoxy<br />

coating 150 microns thick over epoxy primer. Acid / Alkali resistant lining material shall<br />

conform to the following: Bitumen primer shall co conform nform to IS: 158. Bitumastic compound<br />

shall conform to IS: 9510. Where the height of bitumastic layer on vertical surface is more<br />

than 2.0 m, the bitumastic layer shall be reinforced with diamond pattern expanded metal<br />

steel sheets conforming to IS: 412. A. R. tiles shall conform to IS: 4457. Mortar: Potassium<br />

silicate and resin type mortars shall conform to IS : 4832 Parts – I and II respectively.<br />

23.0 FINISHING SCHEDULE<br />

The contractor's scope also includes all doors, windows, glazing, rolling shutters, f ffinishes,<br />

damp proofing, inserts, anchor bolts, embedments, stairs, nosing, railings, toe - guards,<br />

ladders, edge protection angles, etc. The Contractor shall adhere to the finishing schedule as<br />

given.<br />

23.1 Flooring<br />

I. P. S. ( cement concrete flooring ) with metallic hardener topping shall be provided for all<br />

floors in transfer houses, including ground floors of transfer houses, ground conveyors,<br />

operating floor of pump houses, M. C. C. rooms, cable vault / cable spreader rooms,<br />

maintenance enance and unloading areas, general storage areas and all other areas in plant<br />

buildings where heavy duty flooring is required. Heavy Duty Ceramic Tiles ( matt finish ) shall<br />

be provided for toilets, office rooms, laboratories, control rooms and control eq equipment<br />

rooms. Well polished Kota stone shall be provided for staircases, passages, lobbies and<br />

general circulation areas. The floor shall be laid on an already laid and matured concrete<br />

base. Sunken R. C. C. slab shall be provided in toilet area so as to keep the finished floor<br />

level of these areas same as that of the surrounding area Wherever specified metallic<br />

hardener topping shall be 12 mm thick using uniformly graded iron particles, properly<br />

treated. Wherever specified Heavy duty ceramic tiles of siz size e 300 x 300 x 7 mm thick<br />

(minimum) of reputed manufacturer (Kajaria, Spartek or equivalent) of approved finish,<br />

shade and colour to be used. The tiles shall have a scratch resistance of minimum 5 on<br />

Mohr’s scale and shall have a bending strength of 350 Kgs Kgs. . / cm.2 Paving details shall be<br />

similar to grade slab excluding metallic hardener. Skirting in general shall be 150 mm high.<br />

Technical Specification:Sec-7, Civil<br />