25.04.2013 Views

NATIONAL ALUMINIUM COMPANY LIMITED - Rites

NATIONAL ALUMINIUM COMPANY LIMITED - Rites

NATIONAL ALUMINIUM COMPANY LIMITED - Rites

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

** Copper flat of equivalent size can be used instead of aluminium flat.<br />

NOTES : Overload relay shall be selected based on actual full load current and starting time.<br />

GENERAL TECHNICAL PARTICULARS OF MCC<br />

GENERAL<br />

1. System<br />

: 415V, 3 phase, 4 wire, 50 Hz. Solidly earthed neutral<br />

2. Type<br />

: Indoor type, cubicle construction, free standing<br />

3. Pollution degree : 4<br />

4. Creepage distance : As per IS-13947 (1993), Part-I<br />

5. Enclosure<br />

: IP54<br />

6. Mounting<br />

: I/C & B/C in single tier and O/G in multi-tier tier arrangement<br />

execution<br />

7. Neutral earthing : Effectively earthed<br />

8. Control supply : 240V AC / 220 DC for ACB<br />

9. Short time rating : 50 kA for 1 sec<br />

10. Autochangeover required? :Yes<br />

11. Delay drop off required? uired? :Yes<br />

12. Control supply<br />

AIR CIRCUIT BREAKER<br />

: 220 V DC for ACB, 240V AC/220 DC for spring charge motor and<br />

240 V AC for MCCB, etc.<br />

1. Service<br />

2. Type<br />

3. Insulation level : 6 kV (1.2x50 micro Sec) Impulse withsta<br />

4. Utilization Category<br />

5. Operating mechanism<br />

I. Closing<br />

II. Opening<br />

III. Latching<br />

6. Auxiliary Voltage<br />

I. Closing<br />

II. Tripping<br />

CURRENT TRANSFORMERS<br />

1. Type<br />

: Resin cast, window type<br />

2. Rated voltage : 415 V +10%<br />

3. C.T. secondary<br />

4. Accuracy<br />

: 1 Amp rating<br />

i. Protection : 5P10 or better for protection<br />

ii. Metering : Class - 1<br />

Technical Specification:Sec-6, Electrical<br />

: Indoor<br />

: Air – break<br />

: 6 kV (1.2x50 micro Sec) Impulse withstand<br />

: B<br />

: Stored energy type<br />

: Motor wound spring operated<br />

: Shunt trip coil<br />

: Mechanically and electrically trip free arrangement<br />

: DC (85% - 110%)<br />

: DC (70% - 110%)<br />

III. Spring charging : 240V + 10% AC or DC motor<br />

IV. Space heater & Lamp : 240V + 10% AC 50 Hz<br />

7. No. of poles of C.B : 3<br />

Page 18 of 97