Suitable under-carriage carriage fitted with flat rollers shall be provided. The rollers shall have<br />

adequate mechanical ical strength and shall be so designed that the transformer shall roll without<br />

undue effort after it has remained immobile for a long period. The edges of rollers shall be<br />

duly rounded off to permit skidding of transformer on flat surface.<br />

4.7.11 Technical Particulars of HT Transformers (33KV/ (33KV/440V)<br />

1.0 General<br />

1.1 Make<br />

1.2 Type<br />

1.3 Service<br />

1.4 Duty<br />

: Continuous<br />

1.5 Degree of Protection : IP:55<br />

1.6 Reference Standard : IS/IEC Equiv<br />

2.0 Rating<br />

2.1 Rated output<br />

2.2 Quantity<br />

2.3 Type of cooling<br />

2.4 Rated voltage Volt :<br />

H. V.<br />

: 33kv<br />

L. V.<br />

2.5 No. of phases<br />

2.6 Rated Frequency Hz : 50<br />

2.7 Vector group reference : Dyn11<br />

2.8 Connection<br />

H. V.<br />

L. V.<br />

LVn<br />

2.9 Insulation<br />

H. V.<br />

L. V.<br />

2.10 Insulation level kVp/kV<br />

H. V.<br />

L. V.<br />

3.0 Temperature<br />

3.1 Reference ambient temp. : 50 0 C<br />

3.2 Temp. rise over reference ambient<br />

a) Top Oil measured by : 50 0 C Thermometer<br />

b) In winding by<br />

4.0 Tappings<br />

4.1 Type<br />

4.2 Taps<br />

4.3 Taps provided on HV winding : Yes<br />

5.0 Method of earthing : Neutral Grounding Resistor<br />

Technical Specification:Sec-6, Electrical<br />

: Reputed Make<br />

: Two winding<br />

: Outdoor<br />

: As per load calculation<br />

: 2 nos<br />

: ONAN<br />

: 440V<br />

: 3<br />

: Delta<br />

: Star<br />

: Grounded through NGR<br />

: Uniform<br />

: Uniform<br />

: 75/28<br />

: 40/10<br />

:<br />

: 55 0 C Resistance<br />

: Off circuit Tap Changer (OCTC)<br />

: ±10% in steps of 2.5%<br />