The LDBs shall be fabricated from CRCA sheets with 2 mm thickness for all members except<br />

the doors of the modules, the rear covers, the covers of cable chambers and busbar chambers<br />

which may be of 1.6 mm with adequate stiffeners to prevent buckling. Non Non-load bearing<br />

partition walls may be of 1.6 mm thick sheet steel.<br />

The cubicles shall be made up of bolted sheet steel members and side panels of pressed sheet<br />

steel with neoprene gasket at all joints and openings including doors.<br />

Bus bars shall have same cross cross-section section throughout the length. Rating of the neutral bus ba bar<br />

shall be 50% of the main bus bar. Earth bus bar shall run in bottom chamber throughout the<br />

length of the panel.<br />

The LDBs shall have necessary provision at either end for future extension by bolting<br />

additional section.<br />

The busbar shall be supported wi with high quality non-hygroscopic, hygroscopic, insulating, self extinguishing<br />

and fire retardant insulating material, of adequate mechanical strength so as to withstand,<br />

without damage, effects of available short short-circuit circuit current. The busbars shall also be properly<br />

spaced d of facilitate taking vertical connections to individual units. The connections to<br />

individual units shall be taken by taped busbars. The busbars shall be of uniform cross cross-section<br />

and the main busbars shall run throughout the length of the board. Similarly vertical droppers<br />

shall extend for the full height of the panel except the bottom chamber. The connection<br />

between busbars of different metals as well as their connection with the terminals of the<br />

equipment shall be made in such a way to prevent corrosion and local heating.<br />

Liberal space shall be provided for cabling and to accommodate any conventional type of cable<br />

glands for PVC insulated and PVC sheathed armoured aluminum conductor cables.<br />

The cables compartment shall have provision for clamping of ccables<br />

ables inside compartment on<br />

perforated sheet steel sections.<br />

The LDB shall have following meters in each of the two incoming feeders:<br />

• One no. digital type voltmeter with accuracy class of 1.0<br />

• One no. digital type ammeter with accuracy class of 1.0<br />

• One no. digital energy meters with accuracy class of 1.0<br />

Suitable CTs with accuracy class of 1.0 shall be provided in the incomer modules for the above<br />

metering.<br />

Moulded Case Circuit Breakers<br />

LDBs shall have moulded case circuit breaker triple pole, air break type with independent<br />

manual quick make and quick break type. MCCB shall be capable of breaking rated current at<br />

0.3 pf at rated voltage. MCCB shall withstand the fault current envisaged for 415V system and<br />

shall be current limiting type. All outgoin outgoing g feeders shall have earth fault protection.<br />

Technical Specification:Sec-6, Electrical<br />

Page 53 of 97