number of slots in which the switches and ssockets<br />

ockets shall be assembled. The sockets shall be of<br />

three pin design with phase neutral and earth conducts.<br />

Earthing<br />

All electrical equipment shall be effectively earthed as to meet the requirements to Indian<br />

Electricity Rules and IS:3043 IS:3043. . Earthing conductors for individual equipment shall be of either<br />

galvanised mild steel flat or stranded/solid G.I. wire as specified.<br />

Earth pits for street/area lighting poles<br />

The earth pits shall be consisting of 40 NB GI pipe of 3 mtr length, funnel funnel, salt, charcoal, cast<br />

iron cover, clamps, etc. The Bidder shall include all civil work as per requirement. All<br />

accessories shall be included as per requirement.<br />

4.14 LIGHTING HIGH MAST WITH FLOOD LIGHT FITTINGS<br />

General<br />

a. High mast tower for floor ligh lighting ting shall be factory fabricated mild steel plates welded,<br />

polygon section, hot dip galvanized and provided in standard lengths.<br />

b. The structure shall be 30 meter high, well tried, proven design to withstand high wind<br />

speed of 180KM/ hr.<br />

c. The mast shall have ave a movable lantern carriage tower from the top of tower to bottom and<br />

vice-verse verse with the help of a motorised winch arrangement (with motor of minimum 2.2<br />

kW capacity) and shall be provided with suitable gears, pulleys and ropes. The reeling of<br />

ropes shall all be such that to prevent twisting & tangling. Means shall be provided for normal<br />

operation of the winch in case of failure/ non availability of power to the motors. Safety of<br />

lantern carriage in case of breakage of the rope shall be ensured by arresting free fall of the<br />

lantern carriage to the ground by providing Safety locking arrangements.<br />

d. All the carriage components shall be galvanised and mounted inside the tower. The tower<br />

shall be provided with a suitable man entry door at the bottom section to facilitate<br />

inspection and maintenance. The door shall be weather proof and provided with safet safety lock<br />

to prevent unauthorised access.<br />

e. The lantern carriage shall be symmetrical, robust construction housing the luminaire and<br />

control gear boxes. The cables to the luminaries shall be run inside the tubes of the lantern<br />

with junction boxes provided for branch off cables.<br />

f. Proper luminaries carriage ring support arms shall be provided for supporting the<br />

luminaries’ carriage ring when the latter is lowered for maintenance of luminaries. Lantern<br />

carriage ring should be in channel tube and with concealed wwiring<br />

iring the carriage should be<br />

Technical Specification:Sec-6, Electrical<br />