6.0 Neutral grounding Resistor<br />

6.1 Rated current<br />

6.2 Application<br />

6.3 Service<br />

6.4 Resistor material & connection : Punched stainless steel grid element type<br />

6.5 Maximum allowable<br />

over ambient 50 0 allowable temperature rise<br />

C<br />

6.6 Enclosure degree of protection : IP - 55<br />

7.0 System Fault Level<br />

7.1 H. V.<br />

7.2 L. V.<br />

8.0 Conductor material : Electrolytic grade copper<br />

9.0 Creepage distance mm/KV : 3lmm/kV<br />

10.0 Terminal connections<br />

10.1 H. V.<br />

10.2 L. V.<br />

11.0 Marshalling box Degree of protection : IP:55<br />

Power frequency to withstand voltage of 33 KV system should be 75KV.Impulse KV.Impulse test voltage<br />

should be 170KV for system voltage of 33 KV.<br />

4.7.12 Technical Particulars of Dry type transformers (LT)<br />

1. Rated capacity<br />

2. Cooling<br />

3. Duty<br />

4. Voltage ratio (HV/LV)<br />

5. Impedance<br />

6. Winding connection<br />

7. Vector group<br />

8. Termination<br />

9. Tap changer<br />

10.Range of tap changer<br />

11. Short circuit level<br />

12. Earthing system (33 kV)<br />

13. Earthing system (415 V)<br />

14. Bushing CTs<br />

15. Ratio of neutral bushing CTs<br />

16. Impulse test withstand voltage (HT/LT)<br />

17. Power frequency rated short duration<br />

18. Temp. rise above 50 0 C<br />

19. Overload capacity<br />

20. Auxiliary supply voltage<br />

Technical Specification:Sec-6, Electrical<br />

: Less than 100A for 10 seconds<br />

: Grounding through Resistor<br />

: Outdoor<br />

: As per Standards<br />

: 25kA<br />

: 50kA<br />

: Segregated phase bus duct/Cable<br />

: Segregated phase bus duct/Cable<br />

: As per requirement<br />

: AN<br />

: Indoor<br />

: 33/0.440kV<br />

: As per IS<br />

: Delta/star<br />

: Dyn11<br />

: HV : 33KV cable<br />

LV : Cable<br />

: OFTC<br />

: +5% in 5 steps @2.5%<br />

: 25 kA (33kV) for 3 sec<br />

: Low Resistance earthed<br />

kV) : Low Resistance earthed<br />

13. Earthing system (415 V) : Solidly earthed<br />

: On neutral<br />

al bushing CTs : As required for Standby E/F Restricted E/F<br />

16. Impulse test withstand voltage (HT/LT) : As per IS/IEC<br />

17. Power frequency rated short duration : As per IS/IEC withstand voltage (HT/LT)<br />

: 80 0 : As required for Standby E/F Restricted E/F<br />

: As per IS/IEC withstand voltage (HT/LT)<br />

C<br />

: As per ANSI standard<br />

20. Auxiliary supply voltage : 240V AC<br />

Page 38 of 97