17.3 SCOPE<br />

gain into the room, adequate no. of air changes etc. to maintain a uniform temperature and<br />

relative humidity within the air conditioned areas.<br />

17.3.1 Mechanical Ventilation System<br />

The ventilation system generally consisting of adequate number of supply and exhaust air<br />

fans, air filters, ducting along with 3 phase AC motor drives, electricals, supporting<br />

structures, approach/maintenance platforms, civil and structural works and necessary<br />

accessories shall be furnished for ventilating the WT hopper, underground portion of<br />

transfer points, underground conveyor tunnel tunnels s and pent houses. Exhaust fans shall be<br />

provided for Toilets & Battery rooms.<br />

17.3.2 Pressurised Mechanical Ventilation System<br />

The ventilation system generally consisting of adequate number of supply and exhaust fans,<br />

metallic pre filters, HDPE fine fi filters, lters, ducting along with 3 phase AC motor drives, electricals,<br />

supporting structures, approach / maintenance platforms, necessary shed, civil & structural<br />

works and necessary accessories shall be furnished for all MCC/switchgear rooms.<br />

17.3.3 Air Conditioning ioning System<br />

17.3.4 2x100% capacity air conditioning units shall be provided for Wagon Tippler Control Room.<br />

17.3.5 Supply and return air distribution ducting complete with insulation, of resin bonded mineral<br />

wool equivalent of density at least 24 Kg/m Kg/m³ ³ and thermal conductivity of max. 0.49<br />

mw/cm°C conforming to IS:8183 including supporting structures, approach/ maintenance<br />

platforms, civil and structural works and necessary accessories shall be provided.<br />

17.3.6 Air cooled PAC shall be provided provided.<br />

17.3.7 Area around centrifugal fans, filters, motor foundation shall be paved to have a clear<br />

surrounding.<br />

17.4 Codes & Standards<br />

The design, manufacture, inspection and testing of Ventilation & A/C System shall comply<br />

with all the currently applicable statutes, regulations and safety codes in the locality where<br />

the equipment is to be installed. The Ventilation & A/C System shall conform to the latest<br />

edition of the following standards and codes. Other internationally acceptable<br />

standards/codes, which eensure<br />

nsure equal or higher performance than those specified, shall also<br />

be accepted. Nothing in this specification shall be construed to relieve the contractor of the<br />

required statutory responsibility. In case of any conflict in the standard and this<br />

specification, ion, the decision of the Owner Owner/RITES shall be final and binding.<br />

• IS:3588 : Specification for electrical axial flow fans.<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />

Page 47 of 64