Incomer and bus coupler panels<br />

MCC incomers and bus couplers shall have Air circuit breakers. Incomers and bus couplers<br />

shall be rated for at least 125% of maximum de demand mand taking into account the spare feeders<br />

and shall be suitable for the specified fault level.<br />

Incomers and bus coupler shall be electrically interlocked to prevent parallel operation.<br />

However, a definite delay defeat Interlock switch shall be provided to facilitate parallel<br />

operation. Auto changeover facility shall also be provided between the two incomers and bus<br />

coupler.<br />

Feeder Modules<br />

Feeders for motors of 75 kW and above shall be fully drawout type air circuit breakers (ACBs)<br />

with numeric type comprehensive mprehensive motor protection relays. Other motor feeders shall be<br />

consisting of MCCB, contactor, overload relay as main power components to ensure type 2<br />

protection. The short circuit release of MCCBs shall be suitably selected to the applications<br />

concerned.<br />

At least 10% spare feeders (minimum one spare feeder of each type and rating bus sectionwise)<br />

shall be provided. Ammeters with selector switches shall be provided for all continuous /<br />

intermittent running motors beyond 15 kW rated drives.<br />

Busbars and d terminations<br />

Busbars and connection shall be of high conductivity aluminium/aluminium alloy of suitable<br />

hardness and purity complying with as per IS IS-5082-1981. 1981. Busbars shall be insulated by colour<br />

coded heat shrinkable sleeves.<br />

Busbars shall be rated for the nominal current rating of incoming breaker and for the full<br />

short-circuit circuit rating. Earth bus shall run throughout the length of MCC at bottom .<br />

Control bus shall be provided in the bus bar chamber isolated with main bus in all the MCCs.<br />

Similarly power and control terminations shall be in separate chambers in the MCCs. Cable<br />

alley y shall have sufficient space for maintenance and minimum width of cable all alley shall be<br />

300 mm. Shrouding/isolation shall be provided for outgoing power terminations in th the cable<br />

alleys. ys. Modules of MCCs shall be spacious for easy maintenance of the various equipment<br />

inside.<br />

Short circuit strength<br />

Rated short time withstand current shall not be less than 50 kA for 1 second. Rated peak<br />

withstand current not less than 2.1 times the specified short circuit level.<br />

Air circuit breaker (ACB)<br />

Technical Specification:Sec-6, Electrical<br />