4.7.3 Winding<br />

The coils used for transformer winding shall be made of insulated, continuous and smooth<br />

electrolytic copper conductors of high conductivity and of 99.9% purity. Similar coils shall be<br />

connected by accessible joints brazed or welded and finished smooth. No corona discharge<br />

shall result on the winding during induced voltage test as specified in applicable standard.<br />

The insulating materials for dry type transformers shall be of type not inferior to Class “F”. All<br />

insulating materials shall be of proven natu nature re and shall be suitable for the suitable for the<br />

limits indicated in the applicable standards as well as the maximum possible winding<br />

temperature and shall not deteriorate when the transformer is operated continuously at its<br />

specified rating at the specif specified ambient temperature.<br />

The inter-turn and inter-coil<br />

coil insulation shall be so designed that the dielectric stress is<br />

uniformly distributed throughout the winding under all operating conditions.<br />

The windings shall be dry cast resin type.<br />

The transformer er windings shall be designed for basic Impulse insulation level not lower than<br />

those specified above.<br />

4.7.4 Protective Housing for Dry type Transformer<br />

Dry type transformer shall be provided with suitable protective sheet steel housing, with<br />

minimum IP P 23 degree of protection for the enclosure. The housing shall have ventilation<br />

louvers provided with wire mesh screens and shall be supplied with suitable lifting lugs. Safety<br />

limit switches shall be provided and wired in such a way that the incoming supp supply may be<br />

disconnected whenever any one of the sides of the enclosures are opened with the<br />

transformer in energized condition.<br />

Sufficient precautions shall be taken so that doors are closed fully. Door locks shall be<br />

provided and keys shall be universal type.<br />

4.7.5 Off-Circuit Circuit Links<br />

The off-circuit circuit tapping links shall be provided on the HV side with appropriate register plate to<br />

show the link location. The links shall be provided with a separate door for access. The door<br />

shall be provided with appropriate safely limit switches which will trip the transformer HV / LV<br />

sides in open condition.<br />

4.7.6 Cooling<br />

The cooling system for or dry type transformers shall have Air Air-Natural Natural (AN) cooling.<br />

4.7.7 Neutral Bushing Current Transformers<br />

Technical Specification:Sec-6, Electrical<br />

Page 34 of 97