All AC squirrel cage induction motors shall be fed at 415V V from switchboard through air circuit<br />

breakers with numeric type compreh comprehensive motor protection relays via power contactor and<br />

overload relay.<br />

g) System Earthing<br />

33kV system is unearthed, , 415V system is solidly earthed.<br />

2.6 ELECTRICAL SYSTEM REQUIREMENTS<br />

Minimum number of spare feeders in each of the MCC / PDB / LDB / SLDB shall be 10% subject<br />

to minimum one no. of each type and rating in each section. The rating a aand<br />

type of spare<br />

feeder shall be decided during detailed engineering stage.<br />

Sizes and requirement of various power and control cables shall be decided and intimated to<br />

the Purchaser well in advance to suit the approved scheme/to achieve scheme requiremen requirement.<br />

Space heater power supply to the motors shall be fed from the MCC through same cubicle by<br />

415/240 V transformers. Space heaters shall be interlocked with motor main power supply.<br />

Bidder to submit a system wise drive list indicating required process in interlocks, permissive<br />

conditions etc. with places and mode of control, control system philosophy with provision of<br />

various control, indication, measuring devices at various places. The Purchaser Purchaser/RITES shall<br />

approve this based on above approved philosophy an and d Bidder shall have to provide all<br />

equipment / materials and prepare a control scheme/logic diagram which shall be utilized for<br />

designing the motor feeders at 33 kV switchboard and 415 V MCC at Bidder’s end.<br />

Above-mentioned mentioned control philosophy and interlocking logic shall be prepared as per the<br />

technological requirement.<br />

Suitable electrics for all the material handling equipment like hoist, etc shall be provided for<br />

handling the various drives and mechanism.<br />

Warning hooter shall be of brushless type Siren and AC single phase.<br />

All actuators shall be of geared motors.<br />

Complete 24 V system, wherever required, shall be provided by the bidder.<br />

24 V and 230 V AC shall be taken through separate cables. Screene Screened d cables shall be supplied<br />

and used for 24 V power supply.<br />

All the indication lamps shall be LED based with LVGP (Low Voltage Glow Protection) up to 100<br />

V.<br />

All the hoist control panel shall be located at workable height and platform shall be provided<br />

for r each hoist at one point for maintenance purpose.<br />

Technical Specification:Sec-6, Electrical<br />

Page 10 of 97