Necessary distribution board for distribution of power from UPS output t tto<br />

individual<br />

consumers.<br />

Permissible variations for mains power supply system shall be as follows:<br />

Voltage<br />

: + 10 % , -15 %<br />

Frequency<br />

: As per IS<br />

Harmonic distortion<br />

: < 5%<br />

Output of the uninterruptable power supply system while delivering a load of its rated<br />

capacity (P.F of load shall not effect its output) shall have following variations;<br />

Voltage regulation<br />

:1% (For 0-100% load)<br />

Frequency<br />

: (+/-) 0.5% (For 0-100% load)<br />

Efficiency<br />

:Above 80%<br />

100% to 0% and 0% to 100% load : Volt dip +10%<br />

Enclosure and ventilation<br />

Enclosure conforming to IP IP-41 41 class. Units shall be provided with cooling fans and louvers at<br />

the bottom sides. Individual ventilation ducts for eac each h unit shall be provided.<br />

Distribution Board<br />

The DB shall have two buses, main and standby and shall be protected by semiconductor fuses<br />

with fuse monitoring device, bus healthy lamps, voltmeters and ammeters. Each load shall be<br />

fed by two independent feeders. Isolating and buscoupling switches shall be provided.<br />

The enclosure sheet steel thickness shall be 2.0 mm. with cold rolled sheets and 2.5 mm for<br />

hot rolled sheets and enclosure class protection shall be IP IP-54.<br />

TECHNICAL PARTICULARS<br />

1. Application : Uninterruptible Power supply for PLC aand<br />

nd other essential loads<br />

2. Capacity : 200 % of PLC load<br />

3. Degree of protection : IP 54<br />

4. Cable entry : Bottom<br />

5. Input Supply Voltage : 415V+/ 415V+/- 10%, 3 phase 4 wire, 50 Hz +/- 5%<br />

Batteries<br />

1. Type<br />

2. Application<br />

3. Number of cells in each bank in series<br />

4. Ambient temperature<br />

5. D.C. nominal system voltage<br />

6. Ampere hour capacity<br />

7. Charging method proposed<br />

8. Emergency load duration<br />

Technical Specification:Sec-6, Electrical<br />

: VRLA, SMF<br />

: UPS System<br />

3. Number of cells in each bank in series : As per requirement<br />

: Min.temp. :5.0 deg.C Max.temp. :50 deg. C<br />

5. D.C. nominal system voltage : Suitable to inverter system<br />

: Bidder to furnish along with cal calculations<br />

7. Charging method proposed : . Float and boost<br />

8. Emergency load duration : 60 Minutes (battery back up time)<br />

Page 48 of 97