4. A/C & ventilation RRoom<br />

5. Peripheries of buildings<br />

6. Coal conveyor galleries<br />

7. Dust suppression MCC room<br />

8. Junction houses and transfer towers<br />

9. Wagon Tippler System<br />

10. Control room of WT<br />

11. MCC room for WT<br />

12. Roads/streets within battery limit<br />

13. Area/sub areas within battery limit<br />

14. Any other premise coming under the battery limit<br />

The illumination system shall include the following in required quantities:<br />

• Lighting DBs/ Sublighting DBs • Steel tubular poles<br />

• Light fittings with lamps • Switches<br />

• Lighting fixtures and accessories • Conduits & brackets<br />

• Cables and wiring • Hangers & clamps<br />

• Ceiling fans<br />

• JBs<br />

• Receptacles • Timers/photocell<br />

• For street light LED lamps preferable<br />

• High mast system should have Metal Halide Lamps<br />

All lighting in outdoor area such as ccWT<br />

areas, road/street and area lighting as well as<br />

peripheral lighting shall have auto ON/OFF facility with suitable 24 hrs timer. All the light<br />

fittings shall be dust and weather proof.<br />

Illumination levels envisaged for different areas will be as indicate indicated d below:<br />

S.N. Area<br />

1 Switchgear room 250 FTL AC normal lighting DC<br />

emergency lighting<br />

2. Battery room 100 FTL AC normal lighting DC<br />

emergency lighting<br />

3. Transformer room 200 FTL AC normal lighting<br />

4. MCC room 250<br />

lighting<br />

5. WT Control Room 250 FTL AC normal lighting DC<br />

emergency lighting<br />

6. Junction house 200 MH AC normal lighting<br />

7. Conveyor gallery 100 MH AC normal lighting<br />

8. Peripheral lighting 20 MH AC normal lighting<br />

9. Street / road / area lighting 20 SV AC normal lighting<br />

Technical Specification:Sec-6, Electrical<br />

Lux Fitting type Remarks<br />

FTL AC normal lighting DC<br />

emergency<br />

Page 51 of 97