1. Earthing ring mains at WT substation and all the electrical rooms/premises<br />

2. Equipment earthing<br />

3. Transformer neutral earthing prov providing dedicated pits<br />

Bidder shall include complete earthing material including earthing strips, earth electrodes<br />

other accessories for treated earth pits, etc. and carry out earthing ring mains, earth pits,<br />

interconnections, equipment earthing, all assoc associated iated civil works, etc at all the ubstations.<br />

All the connections of earthing ring mains with available underground earthing grid of<br />

respective substation/premise shall be under scope of the Bidder.<br />

Separate dedicated treated earth pits shall be provid provided ed for transformer neutrals. Two nos.<br />

such earth pits shall be provided for each of the transformers. The treated earth pits shall be<br />

consisting of 3 mtr 65 NB GI pipes, funnels, clamps, 3 mtr long 40 mm MS rod electrodes, MS<br />

cover with lifting lugs, assoc associated civil works, etc.<br />

All the equipment located in the WT premises / sub sub-premises e.g. 33 KV switchboard, LT PCCs,<br />

busducts, transformer bodies, charger panels, DCDBs, LDBs, SLDBs, receptacles, control panels,<br />

MCCs, etc shall be connected by the Bidder with earthing ring mains at least two different<br />

points.<br />

Electronic earthing shall be considerd for PLC, etc<br />

Bidder shall also consider earthing of following equipment to be installed by the bidder.<br />

• 33kV kV WT switchboard at WT substation in switchgear cum MCC room<br />

• WT distribution transformers (2 nos.) – Neutral as well as body earthing<br />

• 415 WT SYSTEM PCC at WT SYSTEM substation in switchgear cum MCC room<br />

• Control panel for power distribution equipment at existing WT control room<br />

• LT busducts (2 sets)<br />

• Charger panels, DCDB, etc at WT substation in switchgear cum MCC room<br />

Bidder shall consider earthing ring mains at each electrical premise and connect the electrical<br />

equipment with the rings. The earthing rring<br />

ing mains shall be connected with underground<br />

earthing mats (consisting of 2x40MM dia to be installed by the bidder. . For transformer neutral<br />

earthing, bidder shall consider dedicated plate earthing.<br />

Bidder shall include complete earthing material includin including g earth electrodes, risers, GI earthing<br />

strips, other accessories, etc. and carry out main earth grid mat, earthing ring mains, earth<br />

pits, risers, interconnections, equipment earthing, all associated civil works, etc within battery<br />

limit of the package. All ll the interconnections with other earthing systems of the plant and<br />

with existing systems shall be under scope of the Bidder.<br />

The Bidder shall obtain the actual soil resistivity of the plant area by carrying out soil resistivity<br />

tests and design the earthing thing system accordingly.<br />

Technical Specification:Sec-6, Electrical<br />

Page 66 of 97