12.0 LOADING<br />

For consideration of loads on structures IS : 875 - ‘Code of practice for structural sa safety of<br />

buildings’ shall be followed. In addition to the dead load, live load, equipment load<br />

(including impact / vibration). Temperature loads etc. various loading conditions arising due<br />

to operation and maintenance of equipment shall be considered in the design. The structure<br />

and equipment shall also be designed for seismic loads as per the “Criteria for Earthquake<br />

Resistant Design of Structures and equipment" and the “Criteria for Wind Resistant Design of<br />

Structures and equipment" specified in the Annexu Annexure re A and B respectively in Civil Section,<br />

whichever is governing. Wind and seismic forces shall not be considered to act<br />

simultaneously. The following minimum live loads shall be adopted for the design of various<br />

structures. If actual expected load is more than the specified load, then actual load is to be<br />

considered<br />

a )Roofs 150 Kgs. / Sq. M. for accessible roofs and 75 Kgs. / Sq. M. for non<br />

accessible roofs. In addition to this coal dust load of 150 KKgs.<br />

gs. / sq. m. shall also be<br />

considered.<br />

b ) R. C. C. floors 500 Kgs. / Sq. M.<br />

c ) Stair and balconies 500 Kgs. / Sq. M.<br />

d ) Toilet rooms 200 Kgs. / Sq. M.<br />

e )Chequered plate floors 400 Kgs. / Sq. M.<br />

f ) Walkways ( including walkways in 300 Kgs. / SSq.<br />

q. M.conveyor galleries )<br />

g)Conveyor galleries In addition to the live loads, loads due to cable trays, fire fighting /<br />

service water pipes shall also be considered @ 125 Kgs. / m ( minimum ) on each of the<br />

longitudinal girder. Roof Roof-truss members are to o be checked for supporting fire fighting<br />

pipes/Service water pipes.<br />

h ) Road Culverts and its allied For class 'AA' loading and checked for structures including R.<br />

C. C. pipe class A loading as per IRC standard crossing & road crossing of trenches.<br />

i ) Channels / trenches In addition to earth pressure and water pressure, etc. additional<br />

earth pressure due to surcharge of 2T / Sq. M. shall<br />

j ) Covers for trenches/channels Covers for channels & trenches, shall be designed for a live<br />

load of 0.4T Sq.M. M. &loading mentioned under clause in trenches, whichever is critical.<br />

k ) Sumps and tanks and other In addition to earth pressure with a underground basement<br />

type surcharge of 2T / Sq. M. (or surcharge structures due to Railway loading whichever<br />

is critical for Railway load bearing structures etc.) and sub - soil water pressure etc. These<br />

are also to be designed for the following conditions :<br />

i ) Water / liquid inside and no earth outside (applicable only to such structures which are<br />

liable to be filled up with water or any liquid ).<br />

ii ) Earth with surcharge outside and no water / liquid inside<br />

iii ) For underground (basement) structures protection against buoyancy during execution<br />

and after execution shall be ensured without superimposed loadings with minimum factor<br />

of safety of 1.2 against buoyancy.<br />

l ) Unit weight of coal shallbe taken as 1100 Kgs. / cum. Fordesign purposesIf the er erection<br />

load is higher than the specified live loads on any floor or part thereof,then the erection<br />

loads are to be considered for the design.Permissible increase in stresses of materials and<br />

bearing pressure of soil due to windload or seismic load shall be as per relevant I. R. S. and I.<br />

S. code.<br />

13.0 DESIGN CRITERIA<br />

The loads for all railway load bearing structures e. g. track hopper includingmachinery<br />

hatches, wagon tippler, tunnel and under ground transfer houses etc. and the analysis and<br />

the design of these structures shall be made strictly in accordancewith the pr provisions of<br />

Indian Railway Bridge rules (latest edition), and Indian RailwayCodes of practice (latest<br />

Technical Specification:Sec-7, Civil<br />

Page 10 of 21