Dado in toilets and pantries shall be up to 2.1 m height from finished floor level. Skirting and<br />

dado shall match with the floor ffinish.<br />

23.2 Interior Wall / Ceiling Finish<br />

For all air - conditioned areas and stair case acrylic emulsion paint of approved make and<br />

shade over 2-3 mm cement based putty of approved make shall be provided provided. For toilets<br />

minimum 5 mm thick decorative coloure coloured d ceramic tiles of approved make and shade with<br />

approved pattern up to 2.10 m. height from finished floor level shall be provided. Oil bound<br />

distemper over 2-3 mm cement based putty of approved make above 2.10 m height shall be<br />

provided. For all other area areas s oil bound distemper ( IS : 428 ) of approved shade over cement<br />

based putty of approved make shall be provided. For battery room and other areas coming<br />

in contact with acid / alkali fumes, chemical resistant chlorinated rubber paint shall be<br />

provided above e 2.1 m height. Up to 2.1 m height from finished floor level acid alkali resistant<br />

tiles shall be provided as specified elsewhere. All R. C. C. ceilings shall be oil bound<br />

distemper over cement based putty putty.<br />

23.3 Exterior Finish<br />

Aluminium Industrial troughed sheet cladding ( non - insulated ) of approved colour<br />

combination shall be provided for transfer points, conveyor galleries, elevator shafts, and<br />

parapet walls of buildings where metal cladding is specified. Exterior weathered coat paint<br />

shall be provided for the under mentioned areas :<br />

(a) All buildings with R. C. C. framework unless specified otherwise in this specification<br />

(b) Brick work in the lower portion of metal cladding.<br />

(c) Fire walls<br />

(d) Projections and facia : R. C. C. parapets ( excepting parapets of buildings<br />

(e) where metal cladding is specified )Exterior brick walls.<br />

24.0DOORS, DOORS, WINDOWS AND ROLLING SHUTTERS.<br />

24.1 Doors and Windows<br />

All doors, windows and venti ventilators of control room building and M. C. C. buildings shall have<br />

Electro colour coated (anodised) aluminium frame work with glazing. All doors of office and<br />

toilet areas shall be of factory made pre pre- laminated particle board (M D F exterior grade). All<br />

other buildings shall have steel doors, windows and ventilators. Single glaz glazed panels with<br />

aluminium framework shall be provided as partition between two air - conditioned areas<br />

wherever clear view is necessary. Coal conveyor galleries shall have steel windows of<br />

openable type. The window shutters shall be provided with M. S. louv louvers. All steel doors<br />

shall consist of double plate flush door shutters. The door shutter shall be 45 mm thick with<br />

two outer sheets of 18 G rigidly connected with continuous vertical 20 G stiffeners at the<br />

rate 150 mm centre to centre. Side, top and bottom edges of shutters shall be reinforced by<br />

continuous pressed steel channel with minimum 18G. The door shall be sound deadened by<br />

filling the inside void with mineral wool. Doors shall be complete with all hardware and<br />

fixtures like door closer, tower bolts bolts, , handles, stoppers aldrops, etc. Windows of coal<br />

galleries shall be provided with welded wire fabric of 1.6 mm thick wire as per IS: 4948 and<br />

12 mm x 30 mm mesh size. Wherever functionally required rolling shutters shall be provided<br />

and these shall be electrically ctrically operated. In transfer points, windows near floors shall be steel<br />

and openable types. The window shutters shall be provided with MS louvers. Windows /<br />

ventilators at higher level can be of steel with fixed glazing. All openable windows shall be<br />

provided ovided with suitable stays. All windows and ventilators onground floor of all switchgear<br />

Technical Specification:Sec-7, Civil<br />