supports, pumps, tanks, etc. as required for the satisfactory operation of dust control,<br />

service water & potable water systems shall be furnished by the Contractor.<br />

16.4 Codes and Standards<br />

The design, manufacture, inspection and testing of Dust Co Control ntrol & Miscellaneous Systems<br />

shall comply with all the currently applicable statutes, regulations and safety codes in the<br />

locality where the equipment is to be installed. The Dust Control & Miscellaneous Systems<br />

shall conform to the latest edition of the following standards and codes. Other<br />

internationally acceptable standards/codes, which ensure equal or higher performance than<br />

those specified, shall also be accepted. Nothing in this specification shall be construed to<br />

relieve the contractor of the requir required ed statutory responsibility. In case of any conflict in the<br />

standard and this specification, the decision of the Owner Owner/RITES shall be final and binding.<br />

• IS:778 : Gun Metal gate, globe & check valves for general purpose.<br />

• IS:780 :Sluice valves for water work works purposes (50 to 300 mm)<br />

• IS:1239 : Mild Steel tubes & fittings.<br />

• IS:2379 :Colour for the identification of pipe line.<br />

• IS:2906 :Sluice valves for water work purposes.<br />

• IS:3589 :Electrically welded steel pipes for water, gas & sewage (200 to 2000 mm)<br />

• IS:5312 : Swing check type reflux (non return) valves.<br />

• IS:1520 : Horizontal centrifugal pump for clean, cold fresh water.<br />

• IS:5120 :Centrifugal pump for clean, cold & fresh water.<br />

• ANSI B 31.1:Code for pressure piping.<br />

• Hydraulic institute Standards of U.S.A.<br />

16.5 DESIGN REQUIREMENT<br />

Plain Water Dust Suppression<br />

16.5.1 At specified locations dust suppression system shall be provided which comprises spray<br />

nozzles discharging plain water in a fine spray to capture air borne dust particles and direct<br />

them into the main in coal flow. Water shall be discharged via a pipe work system through<br />

spray heads at the dust suppression zones.<br />

16.5.2 Water shall be drawn from the water storage tank by 2x100% electric motor driven pumps<br />

and discharged into tank from where 2x100% dut duty y electric motor driven pumps shall<br />

discharge the water via a pipe network system through spray heads at the dust suppression<br />

zones. Solenoid valves shall be provided for open/close control of water line to each spray<br />

head. Each spray head shall consist of minimum 4 nos. nozzles. Spray heads shall be<br />

provided at coal loading and receipt zone. Pressure at inlet to spray head shall not be less<br />

than 2.5 Kg/sq.cm(g).<br />

16.5.3 The dust suppression system over the WT hopper shall have a canopy on which fogging<br />

nozzles zzles are fixed at specified distance. Each nozzle header shall be provided with adequate<br />

number of spray nozzles spaced at 500 mm interval so that the entire length & width of the<br />

wagon tippler hopper are covered by a grid of nozzles. Further, the water s sspray<br />

shall be of<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />