Static Transfer Switches<br />

The static transfer switches shall use SCRs and other static devices, for automatic transfer of<br />

load from the Normal source to the Alternate source. The continuous capacity of each static<br />

switch shall be equal to the full load capacity of one inverter. Maximum transfer time including<br />

sensing shall not be more than 1/4 cycle. The transition shall be "make before break" in both<br />

directions. The static switch shall be provided with fuses in both `normal' and `alternat `alternate'<br />

power source. Provision for annunciation of failure of fuse or failure of alternate source shall<br />

be made. The switch shall be provided with surge suppression networks and shall also be rated<br />

to withstand transient voltages upto 150% of rated voltage. Th The e short time rating of the switch<br />

shall be 150% of the rated full load current for two (2) minutes.<br />

Three phase/single phase Transformer and voltage stabilizer<br />

The transformer connection shall preferably be of Le Blanc type with delta connected winding<br />

on the three phase side or of open delta connection type. Other alternatives shall also be<br />

considered, provided the connection has minimum unbalance on the primary side. The<br />

transformer shall be encapsulated in Class B insulation. The transformer shall be adequately<br />

rated for the duty involved. The actual value may be slightly increased to take care of any<br />

losses in the static voltage stabiliser.<br />

The voltage stabiliser shall employ silicon solid state circuitry and shall maintain the specified<br />

output voltage for 0 to 100% load, with maximum input voltage variation as specified specified.<br />

Manual Bypass<br />

Switch The manual bypass switch shall be a four (4) position swit switch. ch. It shall be used to isolate a<br />

static switch from its load and alternate power supply and to take it out of service without<br />

power interruption to the load. It shall be ‘make before break’ type contacts, so that power<br />

supply to the loads is continuous du during ring switch operations. It shall be capable of carrying rated<br />

continuous full load inverter current.<br />

Fault Diagonistic Unit<br />

Unit Fault diagonistic unit shall be provided to supervise UPS operation. Facility to take print<br />

out and recording of important pparameters<br />

arameters shall be provided. All the alarms shall be interfaced<br />

with DDCMIS.<br />

Battery<br />

DC battery shall be VRLA, sealed maintenance free type. Battery capacity should be 500Amp<br />

Hr with float charger of 110 Amps. Float cum boost charger should be 110Amps also. Battery<br />

shall be located in the battery room. Battery shall be suitable to maintain the power supply for<br />

at least 60 minutes (battery back time) in the event of mains failure.<br />

Technical Specification:Sec-6, Electrical<br />