(i) Wherever possible, access shall be provided by means of stairs.<br />

(ii) All walkways and stairs leading to working platforms shall have minimum 800 mm width<br />

of walkways/flight of stair.<br />

(iii) All other walkways and stairs leading to areas for maintenance purpose, or due to<br />

restriction iction of space, shall have a minimum width of 800 mm of walkway/flight of stair,<br />

unless required otherwise.<br />

(iv) Staircases shall be generally designed with slope of approximate 37.5 37.5° with the<br />

horizontal. (In no case the slope shall exceed 40 ° with the horizo horizontal). Intermediate<br />

landings shall be provided wherever required such that vertical rise of each flight does<br />

not exceed 3000mm. Risers in one flight shall be equally spaced.<br />

(v) Walkway floors and stair treads shall be designed with chequered plate (or non non-slip<br />

type plates). Ribbed floor/treads may be provided wherever the possibility of<br />

accumulation of dust exists, taking care that such provisions do not crate a nuisance to<br />

the operating personnel on the shop floor.<br />

(vi) Rise of treads in staircases shall not excee exceed 200 mm.<br />

(vii) A minimum headroom of 2200 mm shall be provided over operating platforms, visitor's<br />

galleries, or other areas with possibility of public gathering. In all other platforms,<br />

walkways and stairs, minimum headroom of 2000 mm shall be provided. Only i iin<br />

special<br />

cases, local headroom of 1800 mm may be allowed (i.e. at intersection with structural<br />

members etc.).<br />

(viii) Cat ladders shall be provided for access, wherever provision of staircase is impractical<br />

due to limitations of space, or the access is required vvery<br />

ery infrequently.<br />

(ix) Wherever the height of cat ladder exceeds 4.0 m, safety cage shall be provided.<br />

Intermediate landing shall be provided to cat ladders such that vertical height of single<br />

rise does not exceed 8.0 m.<br />

(x) Cat ladders shall be designed with follo following provisions:<br />

i. Width of rung = 500 mm<br />

ii. Minimum rise of rung = 250 mm; Maximum rise of rung = 300 mm<br />

iii. Minimum clearance from rung of ladder to back of cage (in case of caged<br />

ladders) = 700 mm<br />

iv. Minimum clearance from the centre of cage all round = 350 mm<br />

v. Slope of cat--ladders:<br />

I. For normal cat cat-ladders, ladders, slope shall be within the range of 75 75°-90° with the<br />

horizontal.<br />

II. For ship-type type ladders (i.e cat cat-ladders ladders with short side handrails) the slope shall be<br />

within the range of 65 65°-75° with the horizontal.<br />

(xi) All walkways, platforms and stairs shall be provided with safety handrails. All handrails<br />

shall be constructed with steel tubes / angles for posts, top and middle rail and<br />

plates/sheets for toe plates. In case of stairs, the toe guards need not be provided.<br />

(xii) The he vertical height of hand hand-railings railings on walkways and stairs shall be minimum 1000 mm<br />

above floor level.<br />

(xiii) Hand-railing railing along edge of roof and gutters shall have a minimum height of 600 mm<br />

over top edge of gutters/sheets. In such hand railings toe guards need not be provided.<br />

(Only top handrail and midrail shall be provided).<br />

Technical Specification:Sec-4,System System Parameters, Operation & Control Philosophy<br />