The starter holders shall be of well tried tried-out out design and of robust construction with provisions<br />

for easy insertion and removal of the starter ensuring correct contacts by means of strong<br />

spring action.<br />

Push button for group switching of lights<br />

The push h buttons (one no. ON and one no. OFF) shall be mounted on cast iron box with<br />

2NO+2NC contacts and terminal block.<br />

Conduits and Conduit Fittings<br />

Surface conduit installation shall be carried out using hot dip / electro galvanised rigid steel<br />

seamed by welding, screwed type, designed, manufactured and tested in accordance with IS<br />

9537. The various conduit accessories like couplers, bends, elbows, reducers, saddles, clamps,<br />

lock nuts, junction boxes etc. shall conform to IS 3837 shall be supplied and erec erected as per<br />

requirement along with the conduits.<br />

Point wiring materials and Accessories<br />

The point wiring materials and accessories for lighting for installation, fan points, sockets etc.<br />

where specified shall include wiring cables, conduits and conduit fittings, wiring accessories<br />

inclusive of switches, sockets, fan regulators, switch boxes, junction boxes etc.<br />

Point wiring<br />

The wiring cables used in point wiring installation shall be 1100 volts grade PVC insulated<br />

single core flexible stranded copper conductor type confirming to IS:694. The size of<br />

conductors to be adopted shall be 2.5 sq.mm for lighting, fan and 5/15A socket outlet circuit<br />

and 2.5 sq.mm for 15A socket power circuits.<br />

Wiring Accessories<br />

The various electrical wiring accessories vi viz. z. Switch boxes, switches and sockets shall confrom<br />

to IS 5133, IS 3854 and IS respectively. The switch boxes shall preferably be of passed sheet<br />

steel cadmium coated and passivated or galvanised with knockouts at the top and the bottom<br />

for conduit entry. The surface mounted type boxes shall have necessary provisions for<br />

mounting on the wall. Earthing terminals shall be provided in the box. Junction boxes provided<br />

at intermediate points shall also be identical in construction to the switch boxes. The switch<br />

and junction boxes shall be of standard dimensions with adequate wiring space. The switches<br />

and sockets shall be made of superior quality engineering plastic with excellent dielectric<br />

properties. The switches shall be of piano key design and shall have ad adequately equately rated switch<br />

contacts. The switch contacts shall be silver tipped electrolytic grade copper. The switch plate<br />

forming part of the switch box cover shall be made of plastic material and shall be made with<br />

Technical Specification:Sec-6, Electrical<br />

Page 61 of 97