socket outlets shall be controlled by rotary type switch mounted flush in the socket outlet box.<br />

Operating handle of the rotary switch shall be fixed in such a manner that it will not be<br />

possible either to insert or to with withdraw draw the plug without switching off the supply. All socket<br />

outlets shall be supplied with heavy duty type plug and cap with chain. The isolating switches<br />

shall be of industrial type of category AC 23. The isolator shall be housed in dust and vermin-<br />

proof sheet heet steel enclosure suitable for terminating aluminum conductor cables either directly<br />

by means of cable gland or through conduits. The current rating for the socket outlets shall be<br />

20 A. Wherever called for HRC fuses shall be incorporated in the socket outlet box.<br />

Inscription plate shall be provided indicating the voltage rating and feeder identifications for<br />

the switch socket outlet.<br />

MCB Controlled Socket Outlet<br />

The MCB controlled socket outlet shall be similar to the above switch socket outlet and<br />

provided with industrial type socket outlet with cover suitable for 240V, 20A single phase AC<br />

and controlled through single pole 20A MCB.<br />

Ceiling Fans and Regulators<br />

Ceiling fans regulators shall be designed, manufactured and tested as per IS:374. The fans shall<br />

have totally enclosed, capacitor start and run motors, suitable for operation on 240V, single<br />

phase, 50 Hz AC system. The electronic type regulator shall have ‘ON’ – ‘OFF’ position next to<br />

the lowest speed contact, shall be provided with necessary harmonic filters and shall be<br />

suitable for operation at 500C ambient temperature.<br />

Down rods required for installation of ceiling fans shall be included by the Bidde Bidder.<br />

Lighting Poles<br />

Steel tubular road lighting poles with single outreach shall be of swaged and welded<br />

construction conforming to IS:2713 IS:2713-1969 with latest amendments.<br />

The outer surface of pole above foundation shall be painted with two coats of red o ooxide<br />

zinc<br />

chromate primer paint as per IS:2713 and finished with two coats of synthetic enamel paint of<br />

approved shall not be less than 100 microns.<br />

The outer surface of the pole embedded in concrete foundation as well as the entire inner<br />

surface shall be e painted with two coats tar based general type black paint.<br />

The poles shall be provided complete with fixing arrangement for loop loop-in in and loop out box and<br />

lighting fittings. The Bidder shall submit a drawing indicating the general arrangement and the<br />

final l design and arrangement shall be subject to purchaser’s approval.<br />

The 415 loop-in loop-out out box shall be weather weather-proof, proof, dust tight, sheet steel enclosure suitable<br />

for outdoor installation. The box shall have hinged front with front locking device. 3 Nos. open<br />

Technical Specification:Sec-6, Electrical<br />