Following power utilization standard voltage levels shall be adopted for various systems:<br />

1. Station supply<br />

3. Power supply to PLC extension 240 V, 1 phase, 2 wire, 50 Hz, A.C. (from UPS)<br />

4. DC control supply<br />

220 V, 2 wire, unearthed<br />

5. Plant illumination<br />

6.<br />

7.<br />

Welding socket / power 415 V, 3 phase, 50 Hz, A.C. outlets<br />

receptacles<br />

240 V, 1 phase, 2 wire, 50 Hz, A.C. outlets<br />

Special socket outlets for 24 V, 1 phase, 2 wire, 50 Hz, A.C. through suitable<br />

portable lamps<br />

transformers<br />

8. Sockets for electrical tools, etc 240 V, 1 phase, 2 wire, 50 Hz, with one point earthed<br />

9 Emergency illumination 220 V DC<br />

d) Permissible variations<br />

The system / unit / plant / equipment shall be designed suitably for following variation in<br />

voltage and frequency;<br />

Permissible variation with rated performance and control<br />

effectiveness maintained<br />

Permissible variation for control and regulation equipment with<br />

rated performance and control quality maintained<br />

Permissible voltage dip at HT switchgear bus during starting of<br />

motor<br />

- 15 % -<br />

Permissible voltage dip at MCC bus during starting of LT motors - 15 % -<br />

e) Symmetrical short circuit ratings<br />

The short circuit ratings of all the equipment like MCCs, motors, PDBs / LDBs, cables, power<br />

socket & lighting cabinets, etc shall be selected keeping in view the fault level capacities of the<br />

Purchaser’s electrical equipment.<br />

The three phase symmetrical short circuit rating at 33 kV level shall be 25 25kA. The three phase<br />

symmetrical short circuit rating at 415 V level shall be 50kA.<br />

The rated short circuit withstand duration for 33 KV shall be 3 sec, whereas for 415 V system,<br />

it shall be 1.0 sec.<br />

f) Criteria for selection of voltage levels ffor<br />

drive motors<br />

Technical Specification:Sec-6, Electrical<br />

33 kV, 3 phase, 3 wire, unearthed system<br />

415 V, 3 phase, 4 wire, solidly earthed<br />

240 V, 1 phase, 2 wire, 50 Hz, A.C.<br />

Voltage Frequency<br />

+/-10% 10% +/-5%<br />

+/- 10 % +/-5%<br />

Page 9 of 97