front design. The distribution board shall be suitable for cable entry from the bottom.<br />

Devices requiring operation sh shall all be located in between 450 mm and 1900 mm from the floor<br />

level .<br />

The ACDB shall have indicating voltmeter with selector switch, PT, MPCB & MCB at the line<br />

side of the distribution board. Ammeter with selector switch, CT, MPCB & MCB shall<br />

also be provided. These instruments shall be flush type located on the front door of the<br />

compartments. The sizes of ammeter and voltmeter shall be 96 mm x 96 mm. Phase<br />

indicating lamps shall be provided vided at the bus side of incomer.<br />

The ACDB shall be fabricated from minimum 2.0 mm thick CRCA sheet steel with load<br />

bearing members comprising 2.5 mm thick CRCA sheet steel. The degree of protection<br />

shall be IP:54.<br />

A the outgoing feeders shall be of MCCB/MCB unit.<br />

Power circuit isolation shall be possible without opening the front door and shall have<br />

provision for padlocking in OFF position with the door closed. ON/OFF indications<br />

shall be provided for a feeders by means of cluster LED lamps.<br />

The main phase busbars and tappings shall be made of aluminium having cross sectional<br />

areas to be substantiated during en engineering gineering but in no case the current density shall<br />

be more than 80 A/sq cm. The busbars shall be suitably supported on non hygroscopic<br />

moulded glass reinforced plastic insulators so as to be capable of withstand withstanding dynamic<br />

forces due to 50 kA through fault short circuit. All joints shall be coloured PVC taped.<br />

Temperature rise of busbars/joints while carrying the rated current shall not be more<br />

than 45°C over maximum ambie ambient nt temperature of 45°C when measured by thermometer.<br />

Tappings from the main busbars to individual feeder compartments shall be by means of<br />

insulated single core copper cables with stranded conductor for feeders upto 100 A ratings<br />

above which aluminium busbars shall be used. All copper to aluminium joints shall be<br />

provided with bimetallic nuts/bolts/washers.<br />

A continuous 50 mm x 10 mm aluminium earth bus shall be provided throughout the<br />

length gth of the panels and shall be located in a separate chamber at the bottom with<br />

removable front cover. Provision shall be kept for taking earth connections to external earth<br />

mat. PVC insulated (Green coloured) copper wires shal shall l be used to connect all noncurrent<br />

carrying metallic parts, doors, etc to the earth bus.<br />

All relays, instruments, meters, pushbuttons, switches and other devices of any feeder<br />

shall be located on the respective compartment only.<br />

All operating handles, control switches, pushbuttons, indicating lamps, instruments, meters<br />

etc shall be mounted on the front of the cubicles.<br />

220 V DC Control Battery Bank<br />

Battery bank shall consist st of plante type lead acid cells in transparent plastic containers<br />

with sufficient quantity of electrolyte, acid level indicating floats, intercell connectors,<br />

cell support insulators, cell number plates, properly ttreated<br />

reated and acid resistant painted<br />

wooden stand supported on porcelain insulators, terminal connectors for external<br />

connections etc. as required to make the installation complete in all respects. The wooden<br />

Technical Specification:Sec-6, Electrical<br />

Page 75 of 97