9. Continuous load/duration : As per requirement<br />

Battery chargers<br />

1. Number required<br />

: 2 nos. (1 FC + 1 FCBC)<br />

2. Type<br />

: Static<br />

3. Method of charging<br />

: Float and boost charge type<br />

4. DC system voltage<br />

: To suit the system<br />

5. Automatic voltage regulator required(AVR) : Yes<br />

6. Regulation with AVR<br />

: +/-1%<br />

7. Permissible harmonics at rated continuous load : +/ +/-2%<br />

8. D.C. load requirement<br />

a) Momentary : As per requirement<br />

c) Continuous : As per requirement<br />

b) Emergency : As per requirement<br />

9. Maximum time for boost charging : 8 Hours<br />

Inverters<br />

1. Type<br />

: Static<br />

2. Suitable for parallel oper : suitable for parallel operation<br />

3. Service<br />

: Indoor<br />

4. Output rating<br />

: As required<br />

5. Output Voltage<br />

: 240 V A.C.<br />

6. Phase<br />

: Single phase<br />

7. Frequency<br />

: 50 Hz<br />

8. Total harmonic content<br />

any single harmonic.<br />

: 5% RMS maximum not more than 3% distort distortion in<br />

9. Duty<br />

: Continuous.<br />

10. Overload capacity<br />

: 125% for 15 minute at 0.8 p.f<br />

11. Efficiency<br />

: Not less than 80% at rated load<br />

12. Cooling<br />

: Natural air cooled<br />

13. Synchronization with source : Yes<br />

Static transfer switch<br />

1. Capacity Continuous<br />

2. Type<br />

3. Voltage<br />

4. Frequency<br />

5. Transfer time<br />

Manual bypass switch<br />

1. Capacity Continuous<br />

2. Type<br />

3. No. of positions<br />

4. Short time rating<br />

5. Transfer<br />

Technical Specification:Sec-6, Electrical<br />

: Make and carry F.L. current of inverter at 0.8 p.f.<br />

: Make before break<br />

: 240V, single phase<br />

: 50 Hz<br />

: 1/4 cycle maximum<br />

: Make and carry F.L. current of inverters at 0.8 p.f.<br />

: Make before break.<br />

: 4<br />

: Short time rating of the inverter for 1Sec & 150% of full load<br />

current for 2 minutes.<br />

: Manual.<br />

Page 49 of 97