All equipment shall be complete with approved safety devices wherever potential hazard to<br />

personnel exists and with provision for safe access of personnel to and around equipment for<br />

operational and maintenance functions. The design shall include all reaso reasonable precautions<br />

and provisions for the safety of operating and maintenance personnel.<br />

Special care shall be taken to make enclosed equipment proof against entry of rats, lizards and<br />

other creeping reptiles which may create electrical short short- circuits inside side live equipment.<br />

MINOR CIVIL WORKS<br />

Minor civil works associated with cabling, earthing, conduit installation, illumination systems,<br />

lighting poles, for buried cables, for erection of equipment supplied by the Bidder, foundation<br />

of lighting masts/poles, es, etc shall be included under scope of bidder. Similarly minor civil works<br />

like widening of floor openings / cable trenches, wall opening for cables, minor chipping, etc<br />

shall be included under scope of bidder.<br />

LOCAL CONTROL STATION<br />

Near all drives local cal control stations shall be provided. Local stations shall have Cast<br />

Aluminium body, dust and vermin proof, and structure mounting. Stat and stop push buttons<br />

shall be mounted on front hinged gasketted and lockable door. Local/remote selector switches<br />

shall all be provided on local control stations. Stop push button shall be lockable type. In addition,<br />

ammeters shall be provided on local control stations for HT drives. Suitable knockouts with<br />

glands shall be provided on the bottom or top cover for cable entry entry. . Terminals shall be suitable<br />

for 2 cores of 2.5 sq.mm conductors with 10% spare terminals. Enclosure shall be conforming<br />

to IP55 with proper rain canopy.<br />

ELECTRICS OF DUST SUPPRESSION SYSTEM<br />

Bidder shall include complete electrics of dust suppression systems coming in the scope within<br />

the battery limit. Bidder shall provide complete electrics including MCC, drives/mechanism,<br />

associated cabling & their termination, local DBs, all power and control ccessories, all related<br />

annunciations, etc.<br />

ELECTRICS OF AIR-CONDITIONING CONDITIONING AND VENTILATION SYSTEM<br />

Bidder shall include complete electrics of air air-conditioning conditioning system and ventilation system.<br />

Complete electrics for the following shall be included:<br />

• Ventilation system for the switchgear cum MCC room at WT SYSTEM substation<br />

• Exhaust fans for the two numbers transformer rooms at WT SYSTEM substation<br />

• Air-conditioning conditioning system for the battery and battery charger room at WT SYSTEM<br />

substation<br />

• Ventilation system stem for dust suppression MCC room<br />

WT SYSTEM ELECTRICS OF HOISTING AND HANDLING EQUIPMENT<br />

Technical Specification:Sec-6, Electrical<br />

Page 70 of 97