<strong>Manual</strong> – TopCon TC.GSS<br />

Installation and commissioning<br />

Commissioning<br />

Usage of an earth leakage circuit breaker<br />

If you want to use an earth leakage circuit breaker, please take note of<br />

the varying requirements for protection against fire and the protection of<br />

individuals.<br />

Regatron recommends the usage of an earth leakage circuit breaker<br />

sensitive to AC and DC leakage currents.<br />

6.2.3.3. DC connection/load connection<br />

The output connections are laid to the rear side of the device as current<br />

bars.<br />

For the load connection you must pay attention to the following aspects:<br />

Use a cable cross-section to suit the device power and nominal<br />

voltage. (See Table 42, unterhalb.)<br />

Screw cable to current bars using cable lugs<br />

Hole diameter: 9 mm<br />

Follow the standards applicable to the related application and type of<br />

cable laying. The values in the table are only a recommendation.<br />

Nominal voltage<br />

on DC side<br />

Cross-section [mm 2 ] – cable on DC side<br />

20 kW device 32 kW device<br />

50 V 95 150<br />

100 V 70 70<br />

200 V 35 50<br />

500 V 16 25<br />

1000 V 6 10<br />

1200 V 6 10<br />

Table 42 Cross-section sizing for the load cable as a function of the output voltage.<br />

For cable lengths of more than 5 m the next size cross-section up<br />

should be selected to keep the voltage drop over the load cable in<br />

limits.<br />