<strong>Manual</strong> – TopCon TC.GSS<br />

7.3.5. Troubleshooting using the HMI<br />

Troubleshooting using the HMI<br />

Warning group and Error group – DISPLAY 26/27<br />

(HMI: Human Maschine Interface)<br />

7.3.5.1. Acknowledging warning and error messages<br />

If error states occur, the electrical power supply changes to the Error<br />

operating state.<br />

The electrical power supply is returned to the Ready state by acknowledging<br />

the error messages ( button on the main screen) if the<br />

reason for the error has been rectified.<br />

Acknowledging will delete all actual warnings and error messages.<br />

Prior to acknowledging, all messages in the error and warning lists<br />

must be analysed. In particular the error and warning sub-groups provide<br />

further, more detailed information on the error or the warning.<br />

7.3.5.2. Error during initialisation<br />

Errors that occur during the initialisation are indicated in a separate<br />

window. After the error window is acknowledged, the main screen appears.<br />

The electrical power supply is in the Error state and the message<br />

Login Error is displayed in the message bar on the main screen. After<br />

eliminating the reason for the error, a restart (switch off and on at the<br />

circuit breaker) is required:<br />

The following initialisation errors are displayed in an error window.<br />

Error Reason and correction<br />

“No call for login”<br />

Table 68 Error description, HMI initialisation (login error)<br />

The internal CAN connection cable between device<br />

and HMI is not correctly connected.<br />

HMI: contact manufacturer.<br />

RCU: check seating of cable connection between<br />

RCU and X101 interface, otherwise contact manufacturer.<br />