<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.14. Error group D) Configuration<br />

Group error: D) Configuration<br />

Flas<br />

hing<br />

code<br />

TopControl/HMI<br />

indication<br />

14-1 D0) Slave ID not<br />

unique<br />

14-2 D1) HMI/RCU ID<br />

not unique<br />

14-3 D2) More than<br />

one master<br />

14-4<br />

in system<br />

D3) Nominal<br />

power of a<br />

slave not<br />

consistent<br />

14-5 D4) Nominal<br />

voltage of a<br />

slave not<br />

consistent<br />

14-6 D5) Nominal<br />

current of a<br />

slave not<br />

consistent<br />

14-7 D6) Number of<br />

devices in<br />

series config.<br />

does not correspond<br />

with<br />

the given<br />

value<br />

14-8 D7) Number of<br />

devices in<br />

parallel config.<br />

does not<br />

correspond<br />

with the given<br />

value<br />

Description<br />

Module ID for a slave<br />

is identical to the<br />

module ID for another<br />

slave<br />

The same HMI/RCU-<br />

ID has been assigned<br />

several times.<br />

More than one master<br />

has been detected<br />

Nominal power of a<br />

module does not match<br />

that of the master<br />

Nominal voltage for a<br />

module does not match<br />

that of the master<br />

Nominal current for a<br />

module does not match<br />

that of the master<br />

The number of devices<br />

in the series or<br />

parallel circuit does<br />

not match the data<br />

specified<br />

Possible reason<br />

Measure to rectify<br />

Each slave requires a unique module ID.<br />

Each HMI/RCU requires a unique HMI-ID<br />

(HMI identifier)<br />

In each system there must be exactly one<br />

TopCon (module ID=0).<br />

10<br />

The nominal data for all modules in a multiunit<br />

system must be identical to those for the<br />

master device<br />

The module IDs have been configured incorrectly<br />

Set module IDs correctly as per instructions<br />

and required configuration<br />

Pre-setting is different to the actual number of modules<br />

in the series or parallel circuit<br />

Connect same number of devices as specified<br />

Adjust setting to the actual number of devices<br />

using TopControl<br />

One or more slaves have not been detected<br />

See above, error C0)<br />

2011-10-18 292 / 298 V00.05b