<strong>Manual</strong> – TopCon TC.GSS<br />

TopControl application<br />

Tab – <br />

Description of the standard scope gridfile<br />

The following signals are arranged as per their group membership<br />

(“group” or “select group”) in the standard gridfile. See Table 103, Seite<br />

208.<br />

Actual values group – “Act.values”<br />

siADC_ActUsense<br />

siCTR_ActImodule<br />

siCTR_ActIsystem<br />

siCTR_ActPmodule<br />

siCTR_ActPsystem<br />

siCRT_ActUmodule<br />

siCTR_ActUsystem<br />

Actual device sense voltage<br />

Value range: 0 – 4000; (4000 ≙ Nominal voltage)<br />

Device role: Valid for master and slave<br />

Actual device output current<br />

Value range: 0 – 4000; (4000 ≙ Maximum current)<br />

Device role: Valid for master and slave<br />

Actual multi-unit system output current.<br />

≙ The sum of all power supplies connected in parallel.<br />

Single device operation: Module current ≙ System current<br />

Value range: 0 – 4000; (4000 ≙ System nominal current)<br />

Refresh: 300 s x number of slaves<br />

Device role: Valid for master<br />

Actual device output power<br />

Value range: 0 – 4000; (4000 ≙ Nominal power)<br />

Device role: Valid for master and slave<br />

Actual multi-unit system output power.<br />

≙ The sum of all power supply powers.<br />

Single device operation: Module power ≙ System power<br />

Value range: 0 – 4000;<br />

(4000 ≙ System nominal power)<br />

Refresh: 300 s x number of slaves<br />

Device role: Valid for master<br />

Actual device output voltage<br />

Value range: 0 – 4000; (4000 ≙ Nominal voltage)<br />

Device role: Valid for master and slave<br />

Actual multi-unit system output voltage.<br />

≙ The sum of all power supplies connected in series.<br />

In single device operation: Module voltage ≙ System voltage<br />

Value range: 0 – 4000;<br />

(4000 ≙ System nominal voltage)<br />

Refresh: 300 s x number of slaves<br />

Device role: Valid for master<br />

Table 104 Description of the variables that are allocated to the “Act.values” group.<br />