<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.3. Error group 2) Output current<br />

Group error: 2) Output current<br />

Flashing<br />

code<br />

3-1 20) i2t<br />

TopControl/HMI<br />

indication<br />

3-2 21) Overcurrent<br />

Isek<br />

3-3 22) Overcurrent<br />

Iprim<br />

3-4 23) Gatedrive A<br />

fault<br />

3-5 24) Gatedrive B<br />

fault<br />

3-6 25) Overcurrent<br />

Isek (level derated<br />

by temperature)<br />

3-7 26) TCLIN Overcurrent<br />

3-8 27) TCLIN Overload<br />

Description<br />

Calculate energy loss<br />

[(Ilimit) 2 – (Iout) 2 ] * t exceeds<br />

limit value I 2 tmax<br />

Output current exceeds<br />

level set for a<br />

specific time.<br />

Transformer current<br />

exceeds level set (level<br />

is temperaturedependent)<br />

Hardware current monitoring.<br />

Short-circuit<br />

detection with direct<br />

shutdown of the power<br />

stage<br />

As for 21) shutdown<br />

level has been reduced<br />

due to high temperature<br />

(from 110% to<br />

100% of maximum<br />

device current)<br />

Current exceeds permitted<br />

limit<br />

Safe Operating Area<br />

limit (SOA) exceeded,<br />

excessively high transients<br />

have occurred<br />

Possible reason<br />

Measure to rectify<br />

Current above Ilimit for a time<br />

Reduce load<br />

Adjust Ilimit or I2tmax to the load<br />

Controller overshooting on set value steps<br />

Reduce set value ramp<br />

Reduce control parameters<br />

Controller oscillation<br />

Reduce control parameters<br />

10<br />

Hard switching of a low resistance load results in current<br />

spikes from the output capacitors<br />

Reduce brief voltage drop by connecting external<br />

capacitor/series indicator<br />

After consultation with the manufacturer, it may be<br />

possible to increase the delay<br />

Controller overshooting on set value steps<br />

Reduce gradient on the set value ramp<br />

Reduce control parameters<br />

Hard switching of a low resistance load (faster and<br />

larger voltage drop)<br />

Reduce brief voltage drop by connecting external<br />

capacitor/series indicator<br />

Reduce control parameters<br />

Hardware fault<br />

Rectification by manufacturer<br />

See above “22) Overcurrent Iprim”<br />

See above “21) Overcurrent Isek”<br />

Reduce load<br />

Controller is unstable<br />

Reduce gain<br />

Reduce drop voltage<br />

2011-10-18 281 / 298 V00.05b