<strong>Manual</strong> – TopCon TC.GSS<br />

TopControl application<br />

Tab – <br />

tab – “Function Block” group (continued)<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

Frequency, text box<br />

Frequency for the base function.<br />

Cannot be applied to user-defined function and with AAP. There the time is<br />

defined individually for each separate point or there is no time dependency.<br />

Value range: 0.001 Hz – 1000 Hz<br />

Symmetry, text box [%]<br />

Ratio between positive signal value and the period, like that for the positive<br />

signal edge for the triangle, or signal pulse for square<br />

Value range: 0 % – 100 %; default 50 %<br />

Rectify Amplitude, check box<br />

To select “Rectify Amplitude” -9- must be selected.<br />

For user-defined and AAP functions this check box cannot<br />

be selected.<br />

(See “Base Function” group -3-).<br />

Selected: Rectification of negative amplitudes (positive values only)<br />

Cleared No rectification.<br />

Bipolar Amplitude, check box<br />

Defines the value range for the base functions:<br />

Sine, square and triangle<br />

Value range (amplitude -4-):<br />

Selected: Function values between - Amplitude and + Amplitude.<br />

Cleared: Function values between 0 and +Amplitude.<br />

Exponential envelope, check box and text box [s]<br />

Activates and deactivates an exponentially decaying amplitude envelope over<br />

the entire length of the function block. The information on the time constant is<br />

given in seconds. Within this time the amplitude falls to 37 %.<br />

The envelope starts after the amplitude has passed the maximum value for<br />

the first time (sine: after ¼ of the first period). In case of user-defined functions,<br />

on the other hand, the envelope starts only after the first period.<br />

The envelope only affects the amplitude, not the offset.<br />

Value range: 0.0001 s – 100000 s, step width: 0.0001 s,<br />

default : 0.0001 s<br />

AAP input filter, list box<br />

Is ready for an entry if in the “Base Function” -3- “AAP” is selected in the list box.<br />

Using the input low pass filter, interference on the signal input (X axis on the<br />

AAP curve) can be filtered out.<br />

Value range: 0.1 Hz – 1600 Hz TP cut-off frequency, default: Off,<br />

Step width: doubling of the previous value<br />

AAP input scale, text box [%]<br />

Is ready for an entry if in the “Base Function” -3- group “APP” is selected in<br />

the list box and “allow manual scaling” is selected.<br />

The curve is compressed on the input side (X axis of the AAP curve) to the<br />

percentage entered.<br />

Value range: 0 % – 100 %, step width 1 %, default: 100 %<br />

Ramp time, text box<br />

For applications see online help using the TopControl button<br />

Value range: 0 – 86400 s; step sequence: 0.001 s; default: 0 s<br />

Table 93 Parameters in the “Function Block” group.<br />