<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.13. Error group C) Login<br />

Group error: C) Login<br />

Flashing<br />

code<br />

TopControl/HMI<br />

indication<br />

13-1 C0) Slave did not<br />

receive CFL 1)<br />

13-2 C1) Slave received<br />

invalid<br />

CFL 1)<br />

13-3 C2) Slave did not<br />

receive EOL<br />

13-4 C3) Slave receivedincomplete<br />

EOL<br />

Description<br />

The slave has not<br />

received a request to<br />

log into the system<br />

Invalid login attempt<br />

Possible reason<br />

Measure to rectify<br />

A master has not been defined<br />

Ensure that a master (module ID=0) is available<br />

Master device was switched on before the slave was<br />

switched on<br />

10<br />

Always switch on master at the same time or after<br />

all slaves (maintain 10-seconf timeout)<br />

Master device was not switched off after the end of the<br />

10s slave timeout<br />

Also switch on master within 10s of switching on the<br />

slaves<br />

Master-slave cable not connected<br />

Check cabling<br />

There is no voltage at the controller board for the master<br />

(LEDs remain off on switching on)<br />

On repeated occurrence contact the manufacturer<br />

TC.GSS power supplies in generation 3 and 4<br />

(TopCon Quadro) are not CAN-compatible<br />

Only use devices in the same generation in a<br />

multi-unit system<br />

Subsequent error for a CAN bus error<br />

See above, error 60/61)<br />

Subsequent error for error C0)<br />

See above, error C0)<br />

Communication error<br />

See above, error 60/61)<br />

1) These errors cannot be detected by the master. They only occur on the slave.<br />

13-5 C4) TCLIN CAN<br />

protocol version<br />

is not identical<br />

13-6<br />

C5) Master did<br />

not receive all<br />

RFL subframes<br />

from slaves<br />

Master and TCLIN<br />

cannot communicate<br />

Missing CAN initialisation<br />

packets detected<br />

TCLIN has a different CAN version to the master<br />

Firmware update on TC.LIN or TC.P master<br />

Communication error during the initialisation phase<br />

See above, error 60/61)<br />

2011-10-18 289 / 298 V00.05b