<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.1. Error group 0) Internal<br />

Group error: 0) Internal<br />

Flas<br />

hing<br />

code<br />

TopControl/<br />

HMI<br />

indication<br />

1-1 00) Invalid systemstate<br />

1-2 01) Invalid<br />

module state<br />

1-3 02) Calculation<br />

Overflow<br />

1-5 04) EEPROM<br />

table write<br />

1-6 05) Flash timeout<br />

1-7 06) ADC<br />

sequence<br />

1-8 07) Invalid EE-<br />

PROM table<br />

1-9 08) Requested<br />

state not available<br />

1-10 09) Thyristor not<br />

switched on<br />

1-11 0A) No active<br />

controller defined<br />

1-12 0B) ADC timeout<br />

1-13 0C) ADC DMA<br />

interrupt missing<br />

1-15 0E) Invalid interrupt<br />

routine<br />

called<br />

1-16 0F) Old<br />

EEPROM table<br />

loaded<br />

Description<br />

Invalid state has been<br />

detected.<br />

For debug purposes<br />

Overflow in internal calculation<br />

trapped<br />

Error on writing the device<br />

parameters to the nonvolatile<br />

memory<br />

Timeout occurred on writing/deleting<br />

a flash sector<br />

AD-converter sequence in<br />

wrong order<br />

Device parameter table<br />

empty or invalid<br />

Unexpected state transition<br />

detected. For debug<br />

purposes<br />

Thyristor for bypassing<br />

the intermediate circuit<br />

charge resistor is not<br />

switched on (nominal<br />

condition).<br />

For debug purposes<br />

An active controller has<br />

not been defined. For<br />

debug purposes<br />

Timeout occurred during<br />

actual value acquisition<br />

Actual value acquisition<br />

incomplete<br />

Unexpected interrupt routine<br />

has been called. For<br />

debug purposes<br />

Version in device parameter<br />

table does not match<br />

actual software<br />

Possible reason<br />

Measure to rectify<br />

On repeated occurrence contact the<br />

manufacturer<br />

10<br />

Wrong parameter set <br />

After a software update ensure that all parameters<br />

supplied have been loaded and saved<br />

Update from V4.11.33 or earlier to V4.11.34 or later<br />

After power up "Store settings" and restart<br />

device.<br />

On repeated occurrence contact the<br />

manufacturer<br />

Heavy EMI pulse affecting AD data stream<br />

Earth devices using large area connections<br />

Locate source of EMI, e.g. contactors without<br />

free-wheeling diodes<br />

On repeated occurrence contact the manufacturer<br />

Subsequent error for error 06<br />

See above, error 06<br />

On repeated occurrence contact the manufacturer<br />

Occurs after a firmware update on the MainDSP<br />

After a software update ensure that all parameters<br />

supplied have been loaded and saved. See also<br />

software update instructions<br />

2011-10-18 278 / 298 V00.05b