<strong>Manual</strong> – TopCon TC.GSS<br />

Operation of the HMI (option)/RCU (option)<br />

VLS settings (page 1) – DISPLAY 24<br />

VLS settings (page 1) – DISPLAY 24<br />

Fig. 84 VLS settings page 1 – DISPLAY 24<br />

VLS settings page 1 – DISPLAY 24<br />

1<br />

2<br />

3<br />

4<br />

5<br />

1<br />

3<br />

5<br />

VLS settings page 1<br />

Input<br />

Function<br />

Action<br />

Output<br />

VLS disabled<br />

upper limit<br />

close relais<br />

warn relais<br />

VLS page 2 ...<br />

Input, menu item<br />

Selection of the actual values to which the VLS function reacts:<br />

VLS disabled: The VLS function is disabled.<br />

DISPLAY 5 and DISPLAY 6 cannot be seen on the DIS-<br />

PLAY.<br />

Voltage: VLS reacts to the actual value for the output voltage.<br />

Current: VLS reacts to the actual value for the output current.<br />

Power: VLS reacts to the actual value for the output power.<br />

Function, menu item<br />

Selection of the thresholds from -1- at which the VLS function reacts:<br />

upper limit: VLS reacts to an upper signal threshold.<br />

lower limit: VLS reacts to a lower signal threshold.<br />

inside window: VLS reacts to signals within threshold window.<br />

outside window: VLS reacts to signals that are outside a threshold window.<br />

Action, menu item<br />

How the switching relay defined in -4- is to react:<br />

open relais: The relay is to open when the state set in -2- occurs.<br />

close relais: The relay is to close when the state set in -2- occurs.<br />

Output, menu item<br />

Which relay is to be operated with VLS.<br />

warn relais, run relais, OK/alarm relais.<br />

VLS page 2 ... , navigation item<br />

Continue to page 2 of the VLS settings – DISPLAY32<br />

Table 64 VLS settings page 1 – DISPLAY 24<br />

2011-10-18 151 / 298 V00.05b<br />

2<br />

4<br />

7<br />

VLS settings page 1<br />

Input<br />

Function<br />

Action<br />

Output<br />

VLS disabled<br />

upper limit<br />

close relais<br />

warn relais<br />

VLS page 2 ...

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!