Appendix<br />
Error list<br />
10.2.2.7. Error group 6) Communication<br />
Group error: 6) Communication<br />
Flashing<br />
code<br />
TopControl/HMI<br />
indication<br />
7-1 60) CAN bus off<br />
7-2 61) CAN error<br />
passive<br />
7-3 62) CAN write to<br />
mailbox<br />
denied<br />
7-4 63) CAN transmission<br />
aborted<br />
7-5 64) CAN receive<br />
message lost<br />
7-6 65) HMI/RCU does<br />
not respond<br />
7-7 66) CAN transmit<br />
queue over-<br />
run<br />
7-8 67) Slave does not<br />
respond<br />
7-9 68) RMB not connected<br />
7-10 69) Slave does not<br />
get data from<br />
master<br />
7-11 6A) TCLIN does<br />
not respond<br />
7-12 6B) TCLIN CAN<br />
error<br />
Description<br />
Possible reason<br />
Measure to rectify<br />
10<br />
CAN controller error CAN bus terminating resistor not connected<br />
A bus terminating resistor is required at both ends<br />
of the bus<br />
Internal conflict between<br />
DSP and CAN controller<br />
The master is not receiving<br />
a response from the<br />
operating panel HMI or<br />
RCU<br />
Internal conflict between<br />
DSP and CAN controller<br />
The master is not receiving<br />
any data from one or<br />
more slaves<br />
Optional external measurement<br />
box (RMB) is not<br />
connected<br />
A slave is not receiving<br />
data from the master<br />
The communication<br />
between TopCon master<br />
and TCLIN has<br />
been interrupted, but<br />
was working before.<br />
General error on the<br />
CAN interface<br />
Master-slave cable not connected correctly.<br />
Ensure all cables on all bus clients are correctly<br />
seated<br />
Inadmissible Y cabling of the CAN bus<br />
In case of stubs keep to the maximum length of<br />
30cm<br />
High levels of interference affect the CAN bus<br />
Locate possible sources of interference and try<br />
switching off<br />
Master-slave cable faulty<br />
Replace cable<br />
Bus clients other than TopCon causing interference on the<br />
bus<br />
Remove all bus clients that are not TopCon masters,<br />
slaves or HMI/RCU<br />
On repeated occurrence contact the manufacturer<br />
Supply voltage too low for related RCU<br />
Check RCU supply voltage<br />
Communication error<br />
See above, error 60/61)<br />
On repeated occurrence contact the manufacturer<br />
Communication error<br />
See above, error 60/61)<br />
Slave has been switched off<br />
Check mains supply for the slave<br />
Supply voltage for the RBM is too low<br />
Check supply voltage<br />
Fibre optic not connected or connected incorrectly<br />
Check correct seating of the fibre optic<br />
Master has been switched off<br />
Check mains supply to the master<br />
Communication error<br />
See above, error 60/61)<br />
Subsequent error for a failed login or an incorrect system<br />
configuration<br />
See below, group error C) and D)<br />
(Also pay attention to any error message from the master)<br />
Connector on the CAN cable is loose.<br />
Connect cable and fasten, re-start system.<br />
Restart system, if necessary contact support<br />