<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.7. Error group 6) Communication<br />

Group error: 6) Communication<br />

Flashing<br />

code<br />

TopControl/HMI<br />

indication<br />

7-1 60) CAN bus off<br />

7-2 61) CAN error<br />

passive<br />

7-3 62) CAN write to<br />

mailbox<br />

denied<br />

7-4 63) CAN transmission<br />

aborted<br />

7-5 64) CAN receive<br />

message lost<br />

7-6 65) HMI/RCU does<br />

not respond<br />

7-7 66) CAN transmit<br />

queue over-<br />

run<br />

7-8 67) Slave does not<br />

respond<br />

7-9 68) RMB not connected<br />

7-10 69) Slave does not<br />

get data from<br />

master<br />

7-11 6A) TCLIN does<br />

not respond<br />

7-12 6B) TCLIN CAN<br />

error<br />

Description<br />

Possible reason<br />

Measure to rectify<br />

10<br />

CAN controller error CAN bus terminating resistor not connected<br />

A bus terminating resistor is required at both ends<br />

of the bus<br />

Internal conflict between<br />

DSP and CAN controller<br />

The master is not receiving<br />

a response from the<br />

operating panel HMI or<br />

RCU<br />

Internal conflict between<br />

DSP and CAN controller<br />

The master is not receiving<br />

any data from one or<br />

more slaves<br />

Optional external measurement<br />

box (RMB) is not<br />

connected<br />

A slave is not receiving<br />

data from the master<br />

The communication<br />

between TopCon master<br />

and TCLIN has<br />

been interrupted, but<br />

was working before.<br />

General error on the<br />

CAN interface<br />

Master-slave cable not connected correctly.<br />

Ensure all cables on all bus clients are correctly<br />

seated<br />

Inadmissible Y cabling of the CAN bus<br />

In case of stubs keep to the maximum length of<br />

30cm<br />

High levels of interference affect the CAN bus<br />

Locate possible sources of interference and try<br />

switching off<br />

Master-slave cable faulty<br />

Replace cable<br />

Bus clients other than TopCon causing interference on the<br />

bus<br />

Remove all bus clients that are not TopCon masters,<br />

slaves or HMI/RCU<br />

On repeated occurrence contact the manufacturer<br />

Supply voltage too low for related RCU<br />

Check RCU supply voltage<br />

Communication error<br />

See above, error 60/61)<br />

On repeated occurrence contact the manufacturer<br />

Communication error<br />

See above, error 60/61)<br />

Slave has been switched off<br />

Check mains supply for the slave<br />

Supply voltage for the RBM is too low<br />

Check supply voltage<br />

Fibre optic not connected or connected incorrectly<br />

Check correct seating of the fibre optic<br />

Master has been switched off<br />

Check mains supply to the master<br />

Communication error<br />

See above, error 60/61)<br />

Subsequent error for a failed login or an incorrect system<br />

configuration<br />

See below, group error C) and D)<br />

(Also pay attention to any error message from the master)<br />

Connector on the CAN cable is loose.<br />

Connect cable and fasten, re-start system.<br />

Restart system, if necessary contact support<br />