<strong>Manual</strong> – TopCon TC.GSS<br />

Options and system options<br />

Hardware options<br />

5.2.2. Integrated safety relay option<br />

Standard applied: EN ISO 13849-1:2006<br />

The flow of up to 32kW of energy is interrupted between the mains connection<br />

and the DC connection by the integrated safety relay.<br />

Interface X107<br />

From<br />

DSP<br />

3<br />

Integrated<br />

safety<br />

Relay<br />

ISR<br />

Pulse Modulator<br />

circuit<br />

1<br />

2011-10-18 77 / 298 V00.05b<br />

24 V<br />

Fig. 42 Diagram of the principle of the energy transfer.<br />

2<br />

primary<br />

side<br />

5<br />

secondary<br />

side<br />

Using a PWM generator -1- a pulse-width controlled AC voltage is generated<br />

-2-. This is applied to the primary side of four transformers. On their secondary<br />

side the supply for the electrically isolated gate driver (IGBT) -4- is generated<br />

via a rectifier and smoothing elements.<br />

The positively driven safety relay -3- interrupts the supply to the primary side.<br />

The pulse-width controlled AC voltage -2- is no longer generated. There is no<br />

further flow of energy on the secondary side. Correct function is ensured by<br />

the positively-driven contacts on the relay.<br />

=<br />

4<br />

IGBT1<br />

IGBT2<br />

IGBT3<br />

IGBT4