<strong>Manual</strong> – TopCon TC.GSS<br />

Appendix<br />

Error list<br />

10.2.2.4. Error group 3) Output voltage<br />

Group error: 3) Output voltage<br />

Flashing<br />

code<br />

TopControl/HMI<br />

indication<br />

Description<br />

4-1 30) Overvoltage Voltage has exceeded<br />

level set for a predefined<br />

time<br />

4-2 31) Max. sense<br />

voltage drop<br />

reached<br />

4-3 32) TCLIN Overvoltage<br />

Possible reason<br />

Measure to rectify<br />

10<br />

Load shedding with high voltage already<br />

Activate load shedding detection<br />

Increase control parameters<br />

Use adaptive control parameters<br />

Connect an additional capacitor<br />

After consultation with the manufacturer,<br />

it may be possible to increase the error delay<br />

Controller oscillation<br />

Reduce control parameters.<br />

Possibly increase P term<br />

Overshooting on set value step<br />

Reduce gradient on the set value ramp<br />

Reduce control parameters<br />

Overshooting with no load: use adaptive<br />

voltage control parameters<br />

Difference between module voltage and sense voltage has exceeded the limit<br />

set for a specific time (delay)<br />

Adjust monitoring level and delay to actual situation.<br />

Possibly deactivate monitoring, if not required<br />

Use lower resistance load feed cable<br />

Do not disconnect load feed cable<br />

Voltage exceeds limit Controller is unstable<br />

Reduce gain<br />

Reduce drop voltage<br />

Reduce input voltage<br />

2011-10-18 282 / 298 V00.05b