SECTION 211000 - FIRE-SUPPRESSION PIPING: continued<br />

C. Grooved-End, Schedule 40 Standard-Weight Steel Pipe: ASTM A53, ASTM A135, or<br />

ASTM A795, hot-dip galvanized where indicated and with factory- or field-formed, squarecut-grooved<br />

ends.<br />

1. Grooved-Joint Piping Systems:<br />

a. Manufacturers:<br />

(1) Central Sprinkler Corp.<br />

(2) Ductilic, Inc.<br />

(3) National Fittings, Inc.<br />

(4) Victaulic Co. <strong>of</strong> America.<br />

b. Grooved-End Fittings: UL-listed, ASTM A536, ductile-iron casting with<br />

OD matching steel-pipe OD.<br />

c. Grooved-End-Pipe Couplings: UL 213 and AWWA C606, rigid pattern, unless<br />

otherwise indicated; gasketed fitting matching steel-pipe OD. Include ductile-iron<br />

housing with keys matching steel-pipe and fitting grooves, prelubricated rubber<br />

gasket listed for use with housing, and steel bolts and nuts.<br />

2.04 IN-BUILDING RISER:<br />

A. An in-building service entrance riser shall be installed as indicated on the drawings. Riser<br />

shall be composed <strong>of</strong> a single extended 90-degree fitting <strong>of</strong> fabricated 304 stainless steel<br />

tubing, maximum working pressure <strong>of</strong> 200 psig. The fitting shall have a flanged connection on<br />

the aboveground outlet and a CIPS coupler on the underground inlet. Ames Fire and<br />

Waterworks series IBR or an approved equal.<br />

2.05 DOUBLE-CHECK BACKFLOW-PREVENTION ASSEMBLIES:<br />

A. Basis <strong>of</strong> Design Product: Subject to compliance with requirements, provide Ames Waterworks<br />

Model Colt 200-BFG or a comparable product by FEBCO, Wilkins or approved equal.<br />

B. UL and FM approved, ASSE 1015 double check valve assembly.<br />

C. Two independent check modules within a single housing, sleeve access port, four test cocks<br />

and two drip tight shut<strong>of</strong>f valves. Check valves shall be removable and serviceable, without<br />

the use <strong>of</strong> special tools. The housing shall be constructed <strong>of</strong> 304 (Schedule 40) stainless steel<br />

pipe with groove end connections. Check valves shall have reversible elastomer discs and in<br />

operation shall produce drip tight closure against the reverse flow <strong>of</strong> liquid caused by<br />

backpressure or backsiphonage.<br />

D. Size: As indicated on the drawings.<br />

E. Configuration: Designed for vertical, straight through flow.<br />

F. Valves: UL and FM approved grooved butterfly valves on inlet and outlet with tamper<br />

switches.<br />

2.06 DIELECTRIC FITTINGS:<br />

A. Assembly shall be copper alloy, ferrous, and insulating materials with ends matching piping<br />

system.<br />

B. Dielectric Unions: Factory-fabricated assembly, designed for 250-psig minimum working<br />

pressure at 180ºF. Include insulating material that isolates dissimilar materials and ends with<br />

inside threads according to ASME B1.20.1.<br />

C. Dielectric Flanges: Factory-fabricated companion-flange assembly, for 175-psig minimum<br />

working-pressure rating as required for piping system.<br />

D. Dielectric Flange Insulation Kits: Components for field assembly shall include CR or phenolic<br />

gasket, PE or phenolic bolt sleeves, phenolic washers, and steel backing washers.<br />