SECTION 265000 - INTERIOR LIGHTING FIXTURES: continued<br />

3.02 INSTALLATION OF INTERIOR LIGHTING FIXTURES:<br />

A. Light fixture locations indicated on electrical drawings are approximate. Architectural<br />

reflected ceiling plans and floor plans define exact locations <strong>of</strong> light fixtures. Install interior<br />

lighting fixtures at locations and heights as indicated, in accordance with fixture manufacturer's<br />

written instructions, applicable requirements <strong>of</strong> NEC, NECA's "Standard <strong>of</strong> Installation,"<br />

NEMA standards, and with recognized industry practices, to ensure that lighting fixtures fulfill<br />

requirements.<br />

B. Provide fixtures and/or fixture outlet boxes with hangers to properly support fixture weight.<br />

Submit design <strong>of</strong> hangers and method <strong>of</strong> fastening, other than that which is indicated or<br />

specified herein, for review by Contracting Officer.<br />

C. Install flush mounted fixtures properly to eliminate light leakage between fixture frame and<br />

finished surface.<br />

D. Provide plaster frames for recessed fixtures installed in other than suspended grid type<br />

acoustical ceiling systems. Brace frames temporarily to prevent distortion during handling.<br />

E. Fasten fixtures securely to structural supports and ensure that pendant fixtures are plumb and<br />

level. Provide individually mounted fluorescent pendant fixtures with pendants longer than<br />

2 feet with twin stem hangers. Provide all pendent stem hangers with ball aligners and<br />

provisions for minimum 1 inch vertical adjustment. Mount continuous rows <strong>of</strong> fixtures with an<br />

additional stem hanger greater than the number <strong>of</strong> fixtures in the row.<br />

F. All recessed light fixtures supported by suspended ceilings shall be securely attached (from a<br />

minimum <strong>of</strong> 4 points) to the structural steel above by four diagonally opposite, adequately<br />

sized safety chains. All support wire shall be same size and strength as the ceiling system<br />

support wires.<br />

G. Tighten connectors and terminals, including screws and bolts, in accordance with equipment<br />

manufacturer's published torque tightening values for equipment connectors. Where<br />

manufacturer's torquing requirements are not indicated, tighten connectors and terminals to<br />

comply with tightening torques specified in UL 486A and the National Electrical Code.<br />

H. Support surface mounted fixtures greater than 2 feet in length at another point in addition to the<br />

outlet box fixture stud.<br />

I. Provide seismic bracing and support such that the light fixtures and/or lamps will not fall<br />

during a Seismic Zone 2A event.<br />

3.03 FIELD QUALITY CONTROL:<br />

A. At the Date <strong>of</strong> Substantial Completion, replace lamps in interior lighting fixtures which are<br />

observed to be noticeably dimmed as judged by the Contracting Officer, after Contractor's use<br />

and testing.<br />

B. Refer to DIVISION 01 for the replacement/restoration <strong>of</strong> lamps in interior lighting fixtures<br />

where used for temporary lighting prior to Date <strong>of</strong> Substantial Completion.<br />

3.04 COMMISSIONING:<br />

A. Clean interior lighting fixtures <strong>of</strong> dust, dirt, and construction debris upon completion <strong>of</strong><br />

installation. Clean fingerprints and smudges from lenses.<br />

B. Protect installed fixtures from damage during the remainder <strong>of</strong> the construction period.<br />

C. Provide new lamps at the start <strong>of</strong> building occupancy by the Contracting Officer.<br />

D. Coordinate with SECTION 017900 - DEMONSTRATION AND TRAINING.<br />

265000-4 DEAN265000.DOC