SECTION 264100 - LIGHTNING PROTECTION SYSTEMS<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section includes lightning protection systems components including, but not limited to,<br />

the following:<br />

1. Air terminals.<br />

2. Bonding plates.<br />

3. Conductors.<br />

4. Connectors.<br />

5. Fasteners.<br />

6. Grounding rods.<br />

7. Splicers.<br />

B. Related Work Specified Elsewhere:<br />

1. Raceways used for lightning protection system conductors are specified in<br />

SECTION 260533 - RACEWAYS.<br />

2. Grounding is specified in SECTION 260526 - GROUNDING.<br />

1.02 REFERENCES:<br />

A. Applicable Standards: Comply with applicable requirements <strong>of</strong> the following standards.<br />

1. American National Standards Institute (ANSI):<br />

a. C2 - National Electrical Safety Code.<br />

2. National Fire Protection Association (NFPA):<br />

a. 780 - Lightning Protection Code.<br />

b. 70 - National Electrical Code.<br />

3. Underwriters Laboratories (UL):<br />

a. 96 and 96A - Lightning Protection Components.<br />

4. Lightning Protection Institute (LPI):<br />

a. 177 - Inspection Guide for LPI Certified Systems.<br />

1.03 SUBMITTALS:<br />

A. Refer to DIVISION 01 and SECTION 260000 - BASIC ELECTRICAL REQUIREMENTS for<br />

administrative and procedural requirements for Submittals.<br />

B. Includes, but not limited to, the following:<br />

1. Product data for each type <strong>of</strong> product specified, including ro<strong>of</strong> adhesive where used.<br />

2. Shop Drawings detailing lightning protection system including, but not limited to, air<br />

terminal locations, bonding locations, raceways, conductor routing, connections, and<br />

grounding.<br />

1.04 SEQUENCING AND SCHEDULING:<br />

A. Coordinate installation <strong>of</strong> lightning protection system with the installation <strong>of</strong> other building<br />

systems and components, including electrical wiring, supporting structures, building materials,<br />

ro<strong>of</strong>, and metal components requiring interface with lightning protection systems.<br />

PART 2 - PRODUCTS<br />

2.01 LIGHTNING PROTECTION SYSTEM COMPONENTS:<br />

A. Provide lightning protection system materials and components that comply with manufacturer's<br />

standard design in accordance with published product information. Provide air terminals,<br />

bonding plates, conductors, connectors, conductor straps, fasteners, grounding rods, rod<br />

DEAN264100.DOC 264100-1