SECTION 230700 - MECHANICAL INSULATION: continued<br />

C. Condensate and Equipment Drain Water below 60ºF:<br />

1. All Pipe Sizes: Insulation shall be any <strong>of</strong> the following:<br />

a. Flexible Elastomeric: 1/2 inch thick.<br />

b. Mineral-Fiber Pipe Insulation, Type I: 1/2 inch thick.<br />

D. Geothermal Water Supply and Return, 200ºF and below:<br />

1. NPS 12 and Smaller: Insulation shall be any <strong>of</strong> the following:<br />

a. Mineral-Fiber, Preformed Pipe, Type I: 1 inch thick.<br />

E. Refrigerant Suction and Hot-Gas Piping:<br />

1. All Pipe Sizes: Insulation shall be any <strong>of</strong> the following:<br />

a. Flexible Elastomeric: 1/2 inch thick.<br />

F. Refrigerant Suction and Hot-Gas Flexible Tubing:<br />

1. All Pipe Sizes: Insulation shall be either <strong>of</strong> the following:<br />

a. Flexible Elastomeric: 1/2 inch thick.<br />

3.19 OUTDOOR, ABOVEGROUND PIPING INSULATION SCHEDULE:<br />

A. All outdoor piping shall receive aluminum field applied jacket.<br />

B. Refrigerant Suction and Hot-Gas Piping:<br />

1. All Pipe Sizes: Insulation shall be any <strong>of</strong> the following:<br />

a. Flexible Elastomeric: 3/4 inch thick.<br />

C. Refrigerant Suction and Hot-Gas Flexible Tubing:<br />

1. All Pipe Sizes: Insulation shall be the following:<br />

a. Flexible Elastomeric: 3/4 inch thick.<br />

3.20 INDOOR, FIELD-APPLIED JACKET SCHEDULE:<br />

A. Install jacket over insulation material. For insulation with factory-applied jacket, install the<br />

field-applied jacket over the factory-applied jacket.<br />

B. If more than one material is listed, selection from materials listed is Contractor's option.<br />

C. Ducts and Plenums, Concealed:<br />

1. None.<br />

D. Piping, Concealed:<br />

1. None.<br />

3.21 OUTDOOR, ABOVEGROUND FIELD-APPLIED JACKET SCHEDULE:<br />

A. Install jacket over insulation material. For insulation with factory-applied jacket, install the<br />

field-applied jacket over the factory-applied jacket.<br />

B. If more than one material is listed, selection from materials listed is Contractor's option.<br />

C. Piping, Exposed Refrigerant Piping:<br />

1. Aluminum, Smooth: 0.024 inch thick.<br />

END OF SECTION 230700<br />

DEAN230700.DOC 230700-19