SECTION 233113 - METAL DUCTS<br />

PART 1 - GENERAL<br />

1.01 SUMMARY:<br />

A. This Section includes metal ducts for supply, return, outside, and exhaust air-distribution<br />

systems in pressure classes from -2- to +10-inch wg. Metal ducts include the following:<br />

1. Rectangular ducts and fittings.<br />

2. Single-wall, round spiral-seam ducts and formed fittings.<br />

B. Related Work Specified Elsewhere:<br />

1. Dampers, sound-control devices, duct-mounting access doors and panels, turning vanes,<br />

and flexible ducts: SECTION 233300 - DUCT ACCESSORIES.<br />

2. For mastics, joint and seam sealant: SECTION 018113 - SUSTAINABLE DESIGN<br />

REQUIREMENTS.<br />

1.02 REFERENCES:<br />

A. Applicable Standards.<br />

1. American Society for Testing and Materials (ASTM):<br />

a. A36A - Carbon Structural Steel.<br />

b. A653 - Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated<br />

(Galvannealed) by the Hot-Dip Process.<br />

c. C920 - Elastomeric Joint Sealants.<br />

2. National Air Duct Cleaners Association (1518 K St., NW, Suite 503, Washington, DC<br />

20005; 202-737-2926; www.nadca.com) (NADLA):<br />

a. 1992-01 - Mechanical Cleaning <strong>of</strong> Nonporous Air Conveyance System<br />

Components.<br />

3. National Fire Protection Association (NFPA):<br />

a. 90A - Installation <strong>of</strong> Air Conditioning and Ventilating Systems (ANSI).<br />

b. 90B - Installation <strong>of</strong> Warm Air Heating and Air Conditioning Systems (ANSI).<br />

4. Sheet Metal and Air Conditioning Contractors' National Association (SMACNA):<br />

a. Duct Cleanliness for New Construction.<br />

b. HVAC Air Duct Leakage Test Manual.<br />

c. HVAC Duct Construction Standards - Metal and Flexible.<br />

d. Seismic Restraint Manual: Guidelines for Mechanical Systems.<br />

5. Underwriters Laboratories Inc. (UL):<br />

a. 723 - Test for Surface Burning Characteristics <strong>of</strong> Building Materials.<br />

1.03 SYSTEM DESCRIPTION:<br />

A. Duct system design, as indicated, has been used to select size and type <strong>of</strong> air-moving and<br />

-distribution equipment and other air system components. Changes to layout or configuration<br />

<strong>of</strong> duct system must be specifically approved in writing by Contracting Officer. Accompany<br />

requests for layout modifications with calculations showing that proposed layout will provide<br />

original design results without increasing system total pressure.<br />

1.04 PERFORMANCE REQUIREMENTS:<br />

A. Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint<br />

construction, reinforcements, and hangers and supports, shall comply with SMACNA's<br />

"HVAC Duct Construction Standards - Metal and Flexible" and performance requirements and<br />

design criteria indicated in "Duct Schedule" Article.<br />

DEAN233113.DOC 233113-1