SECTION 262416 - PANELBOARDS: continued<br />

breakers rated 1,000 amperes or more. Provide breakers with thermal and instantaneous<br />

magnetic trip, with fault-current limiting protection when required and ampere ratings as<br />

indicated. Provide fixed, non-interchangeable trips for circuit breakers rated 15-400A.<br />

Provide fixed, interchangeable magnetic and thermal trips for circuit breakers rated higher than<br />

400A. Construct with over center, trip free, toggle-type operating mechanisms with quickmake,<br />

quick-break action and positive handle trip indication. Construct breakers for mounting<br />

and operating in any physical position, and operating in an ambient temperature <strong>of</strong> 40ºC.<br />

Provide breakers with mechanical screw type removable connector lugs, AL/CU rated.<br />

Provide "SWD" switching duty circuit breakers for all single pole circuit breakers that directly<br />

control (no switch provided) 120 and 277V fluorescent and HID lighting circuits in lighting<br />

panelboards.<br />

G. Accessories: Provide panelboard accessories and devices including, but not necessarily limited<br />

to, ground fault circuit interrupter (GFCI) breakers, integral contactors, feed through lugs, split<br />

bus construction, circuit breaker handle locks, etc., as recommended by panelboard<br />

manufacturer for ratings and applications indicated. Provide circuit breaker handle locks on all<br />

circuits that supply night lights, exit signs, emergency lights, emergency power, energy<br />

management control system (EMCS) panels and fire alarm panels.<br />

H. Metering: CTs, PTs, kWH meter, and instrument phase selector switches as indicated. Mount<br />

meters semi-recessed in front doors and install meter wiring and lacing with sufficient<br />

flexibility at hinged edge <strong>of</strong> meter front mounting plates to prevent damage. Provide the<br />

following meter devices:<br />

1. Volt and ampere meters: Switchboard type, semi-flush unit that is 4-1/2 inches square.<br />

Provide 1% accuracy <strong>of</strong> full scale. Provide black metal trim, white dial, black figures,<br />

and black pointer. Provide ammeters with a 0-5 ampere range (scale as required) and<br />

voltmeters with a 0-150V range (scale as required).<br />

2. Voltmeter transfer switches: Provide a knurled knob handle with a minimum <strong>of</strong> seven<br />

positions (A-B, B-C, C-A, A-N, B-N, C-N and OFF).<br />

3. Ammeter transfer switches: Provide a knurled knob handle with four positions (A, B, C<br />

and OFF).<br />

4. Potential transformers: Provide dry type, 600Vac insulated, 480V primary, 120V<br />

secondary. Provide accuracy to conform to ANSI classification 0.3 W, X, Y with<br />

burdens corresponding to meters connected.<br />

5. Current transformers: Dry type, toroidal brushing (or wound type), ratio as indicated,<br />

secondary terminals connected to short-circuiting-type terminal blocks. Provide thermal<br />

and mechanical ratings corresponding to applied equipment.<br />

6. kWH meters: Provide with mechanical, resettable, pointer type, demand register.<br />

Provide with kW demand pulsed contact closures for remote indication.<br />

PART 3 - EXECUTION<br />

3.01 EXAMINATION:<br />

A. Examine areas and conditions under which panelboards and enclosures are to be installed. Do<br />

not proceed with work until unsatisfactory conditions have been corrected.<br />

3.02 INSTALLATION OF PANELBOARDS:<br />

A. Install panelboards and enclosures as indicated, providing NEC required working space, in<br />

accordance with manufacturer's written instructions, applicable requirements <strong>of</strong> NEC and in<br />

compliance with recognized industry practices to ensure that products fulfill requirements.<br />

262416-4 DEAN262416.DOC